HeatRecoveryUnit

Balanced ventilation with a constant-effectiveness heat recovery and constant-pressure fans (trano's system D); the reference of its air loop

FastSmoothBuildings.Ventilation.HeatRecoveryUnit, model (source)

Purpose

Air handling unit of a balanced ventilation (trano's system D): outdoor air through a heat recovery of constant effectiveness, warmed by constant-pressure fans, and the electricity of the fans metered. The unit is the reference of its air loop: it sets the speed y that the ducts downstream turn into their flows, and the supply air temperature.

Equations

Mixed extract air temperature, regularised by m_flow_small so that it is defined at zero flow (the mean of the port temperatures):

TExt = (∑ ṁi Ti + ṁsmall ∑ Ti/n) / (∑ ṁi + ṁsmall).

Supply air and fans:

TSup = TDryBul + ε (TExt − TDryBul) + ΔTFan,   PFan = y (PSup + PRet),   dEFan/dt = PFan/3.6·106 (kWh),

with the fan powers at nominal flow PSup = ΔpSup ṁnominal/(ρAir ηFan), likewise PRet, and the heating of the supply air by the fans (supply fan after the exchanger, return fan before it) ΔTFan = (PSup + ε PRet) / (ṁnominal cp). The power of constant-pressure fans and the flow are both proportional to y, so ΔTFan is the same at every speed.

Parameters

NameDefaultMeaning
m_flow_nominal nominal supply flow
eps0.8heat recovery effectiveness
dpSup_nominal, dpRet_nominal200 Pa pressure rises of the supply and return fans
etaFan0.5overall efficiency of the fans
m_flow_small10−6 kg/s regularisation of the mixed extract temperature
nPorts_a, nPorts_b1 numbers of extract and supply connections

Use

Connect the weather to weaBus, the supply port_b through a Duct to a Zones.VentilatedZone and its extract back through another duct to port_a, as in Examples.VentilatedRoom.

Parameters

Parameter Type Unit Default Description
nPorts_a Integer 1 Number of extract connections
nPorts_b Integer 1 Number of supply connections
m_flow_nominal Real kg/s Nominal supply flow
eps Real 0.8 Heat recovery effectiveness
dpSup_nominal Real Pa 200 Pressure rise of the supply fan
dpRet_nominal Real Pa 200 Pressure rise of the return fan
etaFan Real 0.5 Overall efficiency of the fans
m_flow_small Real kg/s 1e-6
PSup Real W dpSup_nominal*m_flow_nominal/rhoAir/etaFan Supply fan power at nominal flow
PRet Real W dpRet_nominal*m_flow_nominal/rhoAir/etaFan Return fan power at nominal flow
dTFan Real K (PSup + epsPRet)/(m_flow_nominalcpAir) Heating of the supply air by the fans (supply after the exchanger, return before it)

Revisions