Skip to content

BoilerCircuit

Room heated by a gas boiler and a radiator, in closed loop with pressure-driven flows

FastSmoothBuildings.Examples.BoilerCircuit, model (source)

Extends BaseClasses.PartialHydronicRoom.

The circuit of trano's single-zone hydronic test, in closed loop: a gas boiler held at 80 °C, a pump whose speed follows the opening of the valve, a three-way valve (open: its set point is above the boiler), a radiator and its valve, opened by a PI room controller (21 °C by day, 16 °C at night). The flows follow the pressures of the circuit: a pressure node at the inlet of every component, the pump on its curve. The supply is read by a HeatMeter, which also meters the heat the water leaves in the radiator and its valve (its TExt is the return temperature); EMet is its integral in kWh.