HeatMeter¶
Pass-through: Q_flow is the heat the water carries above the temperature TExt (Buildings HeatMeter)
FastSmoothBuildings.Hydronics.HeatMeter, model (source)
Extends PartialLink.
Purpose
A pass-through that meters the heat the water carries: the flow through the meter times the difference between
its temperature and the temperature TExt of the other pipe of the circuit. On the supply of a
generator, with TExt the return temperature, Q_flow is the heat the generator delivers
to the circuit.
Equations
Q_flow = m_flow cp (TIn − TExt),
T = TOut = TIn,
with m_flow the flow entering the meter and cp = 4184 J/(kg K). The water passes
without delay and without loss.
Set flows and pressure-driven flows
With set flows, what enters leaves. With pressure-driven flows, each outlet has the small linear resistance of
PartialLink: dpLink at the
nominal flow m_flow_nominal, which should be the flow of the branch the meter sits in.
Relation to Buildings
Buildings.Fluid.Sensors.HeatMeter: the same equation, with the same input TExt, without
the dynamics of its temperature sensor. Q_flow is a variable of the meter, not an output connector as
in Buildings: no controller reads it, and the translation into CasADi keeps the variables of a model, not the
outputs of its components. The meter also gives its
temperature T, as
TemperatureSensor, so that it replaces
one.
Use
The supply of Examples.BoilerCircuit,
with the temperature of the water leaving the valve of the radiator as TExt: the heat that measured
data of a heat meter is compared with.
Revisions¶
- November 2026: first version, for the comparison of a simulated house with its heat meter.