PI controller with limits and anti-windup (Modelica LimPID: back-calculation with Ni), its integral relaxed to the reset value while disabled

FastSmoothBuildings.Controls.PI, model (source)

Purpose

A PI controller with limits and anti-windup, and a reset without events: while it is disabled, its integral relaxes to the value that gives the reset output, instead of being reset by a trigger. The limits are smoothLimit, which reaches them exactly.

Equations

With the control error e and the integral I,

yunl = k (e + I),   y = smoothLimit(yunl, yMin, yMax, dY),

dI/dt = enable (e/Ti + (y − yunl) / (k Ni Ti)) + (1 − enable) (yReset/k − e − I) / τReset,   I(0) = yReset/k.

  • enable = 1: the integral of e/Ti, with back-calculation: when the output is limited, y − yunl draws the integral back with the anti-windup gain Ni.
  • enable = 0: the integral relaxes with the time constant tauReset so that the unlimited output tends to yReset; the controller restarts from there when it is enabled again.

enable is a Real and the two parts are blended by it, so it can be the output of a Hysteresis. The output is not multiplied by enable: a model that needs no output while disabled multiplies it, as HeatPumpControl does.

Parameters

NameDefaultMeaning
k, Ti gain and integral time
yMin, yMax0, 1limits of the output
Ni0.9anti-windup gain
yResetyMinoutput after a reset
tauReset30 stime constant of the reset while disabled
dY10−3 (yMax − yMin) half-width of the smooth limits

dY and tauReset are the smoothing of the controller: a calibration or an optimal control problem can widen them.

Relation to the Modelica Standard Library

The limits and the anti-windup of LimPID (back-calculation with Ni); the reset of a trigger is replaced by the relaxation above.

Use

In EmissionPI, HeatPumpControl and HVAC.IdealHeatingCoolingPI. See Validation.PIControl.

Parameters

Parameter Type Unit Default Description
k Real Gain
Ti Real s Integral time
yMin Real 0
yMax Real 1
Ni Real 0.9 Anti-windup gain
yReset Real yMin Output after a reset
tauReset Real s 30 Time constant of the reset while disabled
dY Real 1e-3*(yMax - yMin) Width of the smooth limits

Revisions

  • October 2026: moved from trano's FastModel.Controls.