PartialEmissionControl

Emission control of a zone (trano EmissionControl): set point of its day schedule, output y to the valve or the ideal emitter

FastSmoothBuildings.Controls.PartialEmissionControl, partial model (source)

Purpose

Base class of the emission controls of a zone (trano's EmissionControl): the heating set point TSet from a day schedule, the zone air temperature TZon as input and the output y, the opening of a valve or the share of the power of an ideal emitter. An extending class gives the equation of y.

Equations

TSet = THeaSetBack + (THeaSet − THeaSetBack) occupancy(timeOfDay(t), schedule, dtSet).

occupancy is 1 between the pairs of instants of schedule and 0 otherwise, each change a smooth step over dtSet: the set point changes without an event.

Parameters

NameDefaultMeaning
schedule3600 {7, 19} soccupied between pairs of instants of the day
THeaSet294.15 Kset point when occupied
THeaSetBack289.15 Kset point otherwise
k1gain
dY10−3half-width of the smooth limits of the output
dtSet60 sduration of a change of the set point

dY and dtSet are smoothing widths that a calibration can widen.

Use

Extended by EmissionP, EmissionPI and EmissionOnOff; EmissionMonitored reads its set point as an input instead.

Parameters

Parameter Type Unit Default Description
schedule Real s 3600*{7, 19} Day schedule: occupied between pairs of instants
THeaSet Real K 294.15 Set point when occupied
THeaSetBack Real K 289.15 Set point otherwise
k Real 1 Gain
dY Real 1e-3 Width of the smooth limits of the output
dtSet Real s 60 Duration of a change of the set point

Revisions

  • October 2026: moved from trano's FastModel.Controls.