pumpFlow

Flow of a pump relative to its nominal flow at a head relative to its nominal head: the inverse of the decreasing curve 1.14 - 0.14 x^n through (0, 1.14), (1, 1) and (2, 0.42), zero beyond the shut-off head

FastSmoothBuildings.Utilities.pumpFlow, function (source)

The head of the pump relative to its nominal head, h, falls with the flow relative to its nominal flow, x, as

h(x) = a − k xn,   a = 1.14, k = 0.14, n = log2(0.72/0.14) = 2.3626,

through the points (0, 1.14), (1, 1) and (2, 0.42) of Buildings.Fluid.Movers.Preconfigured.SpeedControlled_y, and decreasing everywhere: each head up to the shut-off head has one flow. The function returns that flow,

x = (positivePart(a − h, 10−4)/k + 10−10)1/n.

Beyond the shut-off head the positive part tends to 0 and so does the flow: a pump against closed valves passes nothing and its head stays near the shut-off head. The floor 10−10 keeps the slope of the root finite where the positive part rounds to zero (a pump at rest against the head of another one).

Use

Hydronics.Pump with pressure-driven flows, with the head scaled to its speed by the affinity laws.

Revisions

  • November 2026: first version. It replaces the parabola through the same three points, which rises from 1.14 to 1.147 between no flow and 0.18 times the nominal flow: beyond its top the pump kept 0.18 times its nominal flow whatever the head, and against closed valves the pressures rose without bound.