6. The residential houses as MPC models: rumoca, CasADi, IPOPT

Question. Do the complex trano houses, with their real systems (a heat pump with a buffer, a gas boiler, a three-way valve, six radiators with thermostatic valves, a ventilation unit, PV), translate to CasADi through rumoca and solve as an optimal control problem with IPOPT?

Answer. Yes, both. The FastSmoothBuildingsMPC model of each house exports in under a minute, IPOPT solves a 12-hour optimal control in 23 to 55 s (Solve_Succeeded), every zone is held at its comfort bound without slack, and the energy meters are recognised as the cost (electricity of the heat pump and fans, PV production; gas of the boiler).

Data: results/mpc_residential_after_renovation.json, results/mpc_residential_before_renovation.json (exports, roles, the trajectories of every control and zone); script scripts/mpc_houses.py; test tests/test_fast_model.py::test_the_optimal_control_heats_the_residential_house (both houses).

Method

trano writes the house with the FastSmoothBuildingsMPC library: the same physics as the closed-loop FastSmoothBuildings, with the controllers removed and their outputs made inputs (*_y.y, bounded to 0..1), and one node per layer boundary in the walls (the closed loop splits the layers as Buildings does). rumoca 0.10.3 translates it into a CasADi ODE (trano-optimization CasadiModel.from_modelica); trano-optimization infers the roles of the inputs and states (the controls, the disturbances, the comfort temperatures TAir, the energy meters and their carriers) and builds a collocated optimal control problem solved by IPOPT. The scenario: 12 hourly steps on a cold, sunless night (0 degC outside, sky at −10 degC, wind 3 m/s), every zone at or above 20 degC, energy at 0.25 per kWh, starting from the initial state of the model (zones at 21 degC).

Results

After renovation (heat pump) Before renovation (gas boiler)
FastSmoothBuildingsMPC export 60 s: 189 states, 28 inputs, 4165 parameters 45 s: 160 states, 27 inputs, 3544 parameters
Closed-loop FastSmoothBuildings export 54 s: 278 states, 19 inputs 42 s: 224 states, 19 inputs
Controls heat pump, three-way valve, ventilation unit, six radiator valves (9) boiler, three-way valve, six radiator valves (8)
Meters and carriers heat pump EEle electricity, fans EFan electricity, PV EPro production boiler EFue fuel
IPOPT Solve_Succeeded in 55 s Solve_Succeeded in 23 s
Comfort slack, largest 0 K 0 K
Lowest zone temperature after 3 h 20.00 degC 20.00 degC
Energy over the 12 h heat pump 0.93 kWh, fans 0.30 kWh gas 57.1 kWh
Cost (0.25 per kWh) 0.31 14.27

What the optimiser does, from the trajectories in the JSON files: both houses let their zones fall from 21 to 20 degC in the first hour and then hold them exactly at the bound. The renovated house first lives on the heat of its buffer and walls (heat pump off for four hours, then rising to 0.20 of its speed), opening the three-way valve and the radiator valves step by step; the old house has no buffer and its walls lose heat fast, so its boiler fires from the first hour (0.19, rising to 0.32 of its power) with the three-way valve fully open on the boiler and the bedroom valves nearly open.

The times are those of this container (4 cores) and include the CasADi construction of the problem; the test of the repository runs both houses in about three minutes.

What made it possible

  • Every component of the library is an explicit, smooth ODE (no events, no algebraic loops), which CasADi and IPOPT need.
  • rumoca 0.10.3 sizes arrays and evaluates subscripts only from literal parameters: the templates write out the sublayer counts and node indices of the walls (nSta, nNod, lay, nod, sub) instead of computing them.
  • The thermostatic valves, the three-way valve and the production become inputs in FastSmoothBuildingsMPC, with the same hydraulics as the closed loop in their set-flow form.
  • The state names of the walls are shared with the closed loop, so that a closed-loop simulation can start the MPC model (closed loop and MPC).