Junction

Split valve: its inlets (port_1) mix, its outlets (port_2, port_3) leave at the mixed temperature; with pressure-driven flows the resistance of Buildings' Junction (dp_nominal[1] at m_flow_nominal[1], linearized) is placed on each outlet

FastSmoothBuildings.Hydronics.Junction, model (source)

Purpose

Split of a circuit into an outlet port_2 and a second outlet port_3 (e.g. the bypass of a ThreeWayValve). The connections of the inlet port_1 mix, and both outlets leave at the mixed temperature T.

Equations

Mixed temperature, with δ = m_flow_small and T̄1 the mean of the inlet temperatures:

T = (∑i wi T1,i + δ T̄1) / (∑i wi + δ),

where wi is the inlet flow with set flows and its positive part with pressure-driven flows.

Set flows and pressure-driven flows

With set flows, the junction conserves mass, ∑ port_1.m_flow + ∑ port_2.m_flow + ∑ port_3.m_flow = 0, and the split between the outlets is set by the rest of the circuit.

With pressure-driven flows, the inlet is a pressure node of small compliance and each outlet connection has the linear conductance G = |m_flow_nominal[1]| / max(dp_nominal[1], dpLink):

port_k[j].m_flow = −G (pin − pk,j),   τhyd G (n2 + n3) dpin/dt = sum of the flows of all ports.

Only dp_nominal[1] and m_flow_nominal[1] enter the equations; when dp_nominal[1] is not positive, the conductance takes dpLink.

Relation to Buildings

The resistance of Buildings.Fluid.FixedResistances.Junction on its first port, dp_nominal[1] at m_flow_nominal[1], linearized and placed on each outlet.

Use

The return of Examples.BoilerCircuit: to the boiler and to the bypass of the three-way valve. Junction2 is the same without the second outlet.

Parameters

Parameter Type Unit Default Description
nPorts_1 Integer 1 Number of connections of the inlet
nPorts_2 Integer 1 Number of connections of the outlet
nPorts_3 Integer 1 Number of connections of the second outlet
m_flow_small Real kg/s 1e-6
pressureDriven Boolean false true: flows from the pressures of the circuit
tauHyd Real s 5 Time constant of the pressure of the inlet node
dp_nominal Real Pa {5000, -1, -1} Pressure drops of Buildings' Junction
m_flow_nominal Real kg/s 0.15*{1, -1, -1} Nominal flows of Buildings' Junction
dpLink Real Pa 1000 Pressure drop at the nominal flow when dp_nominal[1] is not positive
G Real kg/(s.Pa) abs(m_flow_nominal[1])/max(dp_nominal[1], dpLink) Conductance of each outlet (dp_nominal[1], at least dpLink)

Revisions

  • October 2026: moved from trano's FastModel.Hydronics.