IdealHeatingCoolingPI

Ideal heating and cooling of a zone towards day schedules of set points (trano IdealHeatingCooling): a PI controller per mode, limited by the capacities

FastSmoothBuildings.HVAC.IdealHeatingCoolingPI, model (source)

Purpose

Ideal heating and cooling of a zone towards day schedules of set points (trano's IdealHeatingCooling): one PI controller per mode, its output the share of the capacity of that mode, and the energy of each mode metered.

Equations

With T the temperature of heatPortCon (the zone air) and the set points interpolated in their day tables by dayTable,

  • conHea: error TSetHea(t) − T,   QHea = conHea.y QHea,max;
  • conCoo: error T − TSetCoo(t),   QCoo = conCoo.y QCoo,max;
  • dEHea/dt = QHea/3.6·106,   dECoo/dt = QCoo/3.6·106 (kWh);
  • heatPortCon.Q_flow = −(1 − frad) (QHea − QCoo),   heatPortRad.Q_flow = −frad (QHea − QCoo).

Both controllers are always enabled, their outputs between 0 and 1 by smooth limits that reach their bounds exactly: a saturated mode gives no heat at all, and the anti-windup keeps its integral from running away while the other mode works. The schedules are interpolated without events.

Parameters

NameDefaultMeaning
TSetHea[0, 293.15] heating set point: time of day (s) and set point (K)
TSetCoo[0, 300.15] cooling set point: time of day (s) and set point (K)
QHea_flow_max, QCoo_flow_max106 W heating and cooling capacities
k0.1 1/Kgain of both controllers
Ti300 sintegral time of both controllers
frad0radiant share

The controllers keep the other defaults of PI, among them the half-width dY = 10−3 of their limits.

Use

Connect heatPortCon to heaPorAir and heatPortRad to heaPorRad of a zone; the meters EHea and ECoo give the demands. See Examples.IdealHeatingRoom.

Parameters

Parameter Type Unit Default Description
TSetHea Real [0, 293.15] Heating set point: time of day [s] and set point [K]
TSetCoo Real [0, 300.15] Cooling set point: time of day [s] and set point [K]
QHea_flow_max Real W 1e6 Heating capacity
QCoo_flow_max Real W 1e6 Cooling capacity
k Real 0.1 Gain [1/K]
Ti Real s 300 Integral time
frad Real 0 Radiant share

Revisions

  • October 2026: moved from trano's FastModel.HVAC.