PV array (Buildings PVSimpleOriented): P = AfActetaeta_DCAC(HDir + HDif)

FastSmoothBuildings.Electrical.Photovoltaic, model (source)

Purpose

Electrical power of a photovoltaic array of area A, azimuth azi and tilt til, proportional to the irradiance on its plane (TiltedSurface):

P = A fact η ηDC/AC (Hdir + Hdif),

with the fraction of the area with active cells fAct, the module efficiency eta and the efficiency of the inverter eta_DCAC, all constant. The meter EPro integrates the production in kWh.

Relation to Buildings

The power of Buildings' PVSimpleOriented. The model has no electrical connector: the power is the variable P.

Use

Examples.Photovoltaics.

Parameters

Parameter Type Unit Default Description
A Real m2 Area of the modules
eta Real 0.12 Module conversion efficiency
fAct Real 0.9 Fraction of the area with active cells
eta_DCAC Real 0.9 Efficiency of the conversion from DC to AC
til Real rad Tilt
azi Real rad Azimuth: 0 south

Revisions

  • October 2026: moved from trano's FastModel.Electrical.