EmissionPI

Variant default: PI heating loop of Buildings G36 ControlLoops (k = 0.1, Ti = 900 s)

FastSmoothBuildings.Controls.EmissionPI, model (source)

Extends PartialEmissionControl.

Purpose

Emission control of a zone, trano's default variant: the PI heating loop of the G36 control sequences of Buildings (ControlLoops) towards the scheduled set point of PartialEmissionControl.

Equations

y = conHea.y, the output of a PI controller always enabled, with the error e = TSet − TZon, its output limited to [0, 1] by smooth limits of half-width dY and its integral held back by the anti-windup.

Parameters

kHea = 0.1 and TiHea = 900 s, the gain and integral time of the loop; dY = 10−3; the gain k of the base class is not used.

Use

Opens the valve of the radiator of Examples.BoilerCircuit.

Parameters

Parameter Type Unit Default Description
kHea Real 0.1 Gain of the heating loop
TiHea Real s 900 Integral time of the heating loop