EmissionPI¶
Variant default: PI heating loop of Buildings G36 ControlLoops (k = 0.1, Ti = 900 s)
FastSmoothBuildings.Controls.EmissionPI, model (source)
Extends PartialEmissionControl.
Purpose
Emission control of a zone, trano's default variant: the PI heating loop of the G36 control sequences of Buildings
(ControlLoops) towards the scheduled set point of
PartialEmissionControl.
Equations
y = conHea.y, the output of a PI
controller always enabled, with the error e = TSet − TZon, its
output limited to [0, 1] by smooth limits of half-width dY and its integral held back by the
anti-windup.
Parameters
kHea = 0.1 and TiHea = 900 s, the gain and integral time of the loop; dY =
10−3; the gain k of the base class is not used.
Use
Opens the valve of the radiator of Examples.BoilerCircuit.
Parameters¶
| Parameter | Type | Unit | Default | Description |
|---|---|---|---|---|
| kHea | Real | 0.1 | Gain of the heating loop | |
| TiHea | Real | s | 900 | Integral time of the heating loop |
Revisions¶
- October 2026: moved from trano's
FastModel.Controls.