Hysteresis

y goes to 1 when u rises above uHigh and back to 0 when u falls below uLow (CDL Hysteresis), as a bistable state switching within tau

FastSmoothBuildings.Controls.Hysteresis, model (source)

Purpose

A hysteresis without events: the output y goes to 1 when the input u rises above uHigh and back to 0 when it falls below uLow. Instead of the pre(y) of a switching hysteresis, the memory is a state with two stable values, and the threshold is crossed by regStep instead of an if: the model stays an explicit ODE that CasADi and IPOPT can differentiate.

Equations

τ dy/dt = regStep(u − uthr, 1, 0, dU) − y,   uthr = uHigh + (uLow − uHigh) y,   y(0) = y_start.

The threshold moves with the output: it is uHigh at y = 0 and uLow at y = 1. For uLow + dU < u < uHigh − dU, both y = 0 and y = 1 are equilibria and the output keeps the one it is at. When u comes within dU of the threshold, the target of y leaves its value; as y moves, the threshold moves away from u and the switch completes, y relaxing to its new value with the time constant τ.

Parameters

NameDefaultMeaning
uLow, uHigh thresholds of the switches to 0 and to 1
tau10 sswitching time
dU(uHigh − uLow)/10 half-width of the smooth transition at each threshold
y_start0initial output

tau and dU are the smoothing of the switch: the defaults reproduce a switching hysteresis, and a model exported for calibration or optimal control can lengthen tau and widen dU. The band where the output is held is not empty only while dU < (uHigh − uLow)/2.

Relation to Buildings

The Hysteresis block of CDL, with the output a Real state between 0 and 1 instead of a Boolean.

Use

The output is the variable y, read as hys.y; u is usually bound in the declaration. It switches the on/off emission control EmissionOnOff, the demand of BoilerDemand, the pump of CollectorControl and the heating season and buffer charging of HeatPumpControl. See Validation.Hysteresis.

Parameters

Parameter Type Unit Default Description
uLow Real Threshold of the switch to 0
uHigh Real Threshold of the switch to 1
tau Real s 10 Switching time
dU Real (uHigh - uLow)/10 Half-width of the smooth transition of the switch
y_start Real 0 Initial output

Revisions