Hydronics

Water circuits after Buildings.Fluid. Two modes, set by the evaluated parameter pressureDriven of every component: set flows (each valve sets the flow of its branch, the production closes the balance: the model of optimal control), or pressure-driven flows (closed-loop simulation: a pressure node at the inlet of every component, the flow of every outlet from its conductance, the pumps on their curves, as the linearized circuits of Buildings)

FastSmoothBuildings.Hydronics, package (source)

Class Description
PartialFlow Water ports as arrays, one element per connection: the inlets mix, every outlet leaves at TOut; with pressure-driven flows, the inlets meet in a pressure node of small compliance
PartialConserving Mass is conserved: what enters leaves
PartialLink Pressure-driven outlets of a component without resistance in Buildings: a small linear one, dpLink at the nominal flow of each outlet. It must stay small against the branches it feeds: at 1000 Pa, the manifold of six radiators of the renovated house took a fifth of the head of the living room branch, whose valve then opened fully a third more often than in Buildings
Pipe Pass-through (junctions, sensors, pumps without a power model)
TemperatureSensor Pass-through: T is the water temperature
Pump Pump: pass-through with set flows; with pressure-driven flows, the flow at its head from the curve of Buildings.Fluid.Movers.Preconfigured.SpeedControlled_y (1.14, 1 and 0.42 times dp_nominal at 0, 1 and 2 times the nominal flow), scaled to the speed y by the affinity laws
Valve Two-way valve: sets the flow of its branch to y*m_flow_nominal (set flows), or opens to y as Buildings.Fluid.Actuators.Valves.TwoWayEqualPercentage, linearized (pressure-driven flows)
ThreeWayValve Mixing valve: the share y of the outlet flow comes from port_1 (supply), 1 - y from port_3 (set flows), or Buildings.Fluid.Actuators.Valves.ThreeWayEqualPercentageLinear, linearized: port_1 equal-percentage on y, port_3 linear on 1 - y (pressure-driven flows)
Junction Split valve: its inlets (port_1) mix, its outlets (port_2, port_3) leave at the mixed temperature; with pressure-driven flows the resistance of Buildings' Junction (dp_nominal[1] at m_flow_nominal[1], linearized) is placed on each outlet
Junction2 Split valve without bypass: its inlets (port_1) mix, its outlets (port_2) leave at the mixed temperature
radiatorConductance UAEle of Buildings RadiatorEN442_2: the conductance of each element giving the nominal power (bisections)
Radiator EN 442 radiator (Buildings RadiatorEN442_2): nEle water and metal elements in series
Boiler Boiler (Buildings BoilerPolynomial): water and metal heated by the part load ratio y; with set flows, the reference of its circuit (no mass balance)
HeatPumps Performance data of heat pumps (Buildings.Fluid.HeatPumps.ModularReversible.Data.TableData2D)
HeatPump Air-to-water heat pump (Buildings ModularReversible AirToWaterTableData2D, Vitocal 251-A08 scaled to its capacity) charging a mixed buffer; with set flows, the reference of its circuit (no mass balance)

Water circuits after Buildings.Fluid, with set flows (optimal control) or pressure-driven flows (closed loop), as the parameter pressureDriven of every component sets (see Conventions).