ASHRAE 140 (BESTEST) validation
The building models trano generates are validated against the 27 cases of section 5.2 of ASHRAE
Standard 140-2020 (the BESTEST single-zone cases): a 8 m x 6 m x 2.7 m zone in Denver with light
or heavy constructions, 12 m2 of double glazing, 0.414 air changes per hour of infiltration and
200 W of internal gains, with variants for the insulation, the glazing, the window orientation,
overhangs and side fins, an unconditioned sun-space, free-floating temperatures, a dual set point
ideal system with set-backs and night ventilation.
Each case is a trano YAML file (validation/bestest/cases/), simulated for a year with each
library. The annual heating and cooling loads must fall inside the acceptance limits of the
standard; the peak loads and the free-floating temperatures must fall inside the spread of the
reference programs (BSIMAC, CSE, DeST, EnergyPlus, ESP-r, TRNSYS) widened by 5 % of the largest
peak or 1 K. Buildings, IDEAS and FastSmoothBuildings are gating libraries: pytest -m bestest fails when
one of their cases leaves its band, except for the deviations listed below with their reason;
FastSmoothBuildings, the reduced library of trano that translates to CasADi, has its own section.
The reduced-order (AixLib) and ISO 13790 zones are shown for information: ISO 13790 is a monthly
method applied hour by hour and the reduced-order zone still deviates on several cases, so
neither gates. Cases a library cannot describe (shading with IDEAS, which OpenModelica cannot
compile for IDEAS 3.0.0; shading, sun-space and night ventilation with the two simplified zones)
are left out. The tables are rendered from the last results with
python -m validation.bestest report --docs. A walk through the BESTEST cases explains a few
cases in detail: what they are, what is expected, how the YAML describes them and how the results
compare.
Buildings
| Case |
KPI |
trano |
Band |
Reference mean |
Status |
| 600 |
annual_heating |
4.449 MWh |
3.750 to 4.980 |
4.213 |
pass |
| 600 |
annual_cooling |
5.973 MWh |
5.000 to 6.830 |
5.856 |
pass |
| 600 |
peak_heating |
3.215 kW |
2.852 to 3.527 |
3.183 |
pass |
| 600 |
peak_cooling |
6.187 kW |
5.098 to 6.805 |
6.024 |
pass |
| 610 |
annual_heating |
4.475 MWh |
3.610 to 5.270 |
4.311 |
pass |
| 610 |
annual_cooling |
4.810 MWh |
2.740 to 6.030 |
4.256 |
pass |
| 610 |
peak_heating |
3.216 kW |
2.853 to 3.528 |
3.168 |
pass |
| 610 |
peak_cooling |
6.082 kW |
5.009 to 6.754 |
5.861 |
pass |
| 620 |
annual_heating |
4.563 MWh |
3.670 to 5.380 |
4.413 |
pass |
| 620 |
annual_cooling |
4.087 MWh |
2.760 to 5.190 |
4.090 |
pass |
| 620 |
peak_heating |
3.248 kW |
2.869 to 3.554 |
3.186 |
pass |
| 620 |
peak_cooling |
4.700 kW |
3.715 to 5.037 |
4.526 |
pass |
| 630 |
annual_heating |
4.746 MWh |
3.690 to 6.120 |
4.822 |
pass |
| 630 |
annual_cooling |
3.320 MWh |
1.080 to 4.420 |
2.814 |
pass |
| 630 |
peak_heating |
3.250 kW |
2.870 to 3.557 |
3.203 |
pass |
| 630 |
peak_cooling |
4.250 kW |
3.315 to 4.423 |
3.963 |
pass |
| 640 |
annual_heating |
2.715 MWh |
1.580 to 3.760 |
2.612 |
pass |
| 640 |
annual_cooling |
5.725 MWh |
4.440 to 6.860 |
5.636 |
pass |
| 640 |
peak_heating |
4.356 kW |
3.806 to 4.891 |
4.369 |
pass |
| 640 |
peak_cooling |
6.138 kW |
5.044 to 6.750 |
5.973 |
pass |
| 650 |
annual_heating |
0.000 MWh |
0.000 to 0.000 |
0.000 |
pass |
| 650 |
annual_cooling |
4.802 MWh |
3.460 to 5.880 |
4.644 |
pass |
| 650 |
peak_heating |
0.000 kW |
0.000 to 0.000 |
0.000 |
pass |
| 650 |
peak_cooling |
5.949 kW |
4.731 to 6.604 |
5.813 |
pass |
| 660 |
annual_heating |
3.620 MWh |
2.680 to 4.820 |
3.713 |
pass |
| 660 |
annual_cooling |
3.315 MWh |
1.910 to 4.330 |
3.172 |
pass |
| 660 |
peak_heating |
2.728 kW |
2.472 to 3.103 |
2.801 |
pass |
| 660 |
peak_cooling |
3.629 kW |
3.146 to 4.130 |
3.565 |
pass |
| 670 |
annual_heating |
6.473 MWh |
4.000 to 7.960 |
5.681 |
pass |
| 670 |
annual_cooling |
6.361 MWh |
5.050 to 7.670 |
6.402 |
pass |
| 670 |
peak_heating |
4.294 kW |
3.444 to 4.432 |
3.943 |
pass |
| 670 |
peak_cooling |
6.560 kW |
5.493 to 7.271 |
6.445 |
pass |
| 680 |
annual_heating |
2.227 MWh |
1.210 to 3.080 |
2.056 |
pass |
| 680 |
annual_cooling |
6.136 MWh |
5.130 to 7.700 |
6.264 |
pass |
| 680 |
peak_heating |
2.013 kW |
1.672 to 2.232 |
1.984 |
pass |
| 680 |
peak_cooling |
6.518 kW |
5.408 to 7.404 |
6.446 |
pass |
| 685 |
annual_heating |
4.932 MWh |
4.080 to 5.750 |
4.762 |
pass |
| 685 |
annual_cooling |
8.946 MWh |
7.700 to 10.140 |
8.886 |
pass |
| 685 |
peak_heating |
3.225 kW |
2.863 to 3.543 |
3.183 |
pass |
| 685 |
peak_cooling |
6.932 kW |
5.713 to 7.517 |
6.743 |
pass |
| 695 |
annual_heating |
2.768 MWh |
1.700 to 3.810 |
2.656 |
pass |
| 695 |
annual_cooling |
8.754 MWh |
7.490 to 10.580 |
8.912 |
pass |
| 695 |
peak_heating |
2.047 kW |
1.688 to 2.245 |
2.001 |
pass |
| 695 |
peak_cooling |
7.080 kW |
5.855 to 7.918 |
6.979 |
pass |
| 900 |
annual_heating |
1.718 MWh |
1.040 to 2.280 |
1.627 |
pass |
| 900 |
annual_cooling |
2.395 MWh |
2.350 to 2.600 |
2.467 |
pass |
| 900 |
peak_heating |
2.668 kW |
2.304 to 2.917 |
2.591 |
pass |
| 900 |
peak_cooling |
2.974 kW |
2.387 to 3.545 |
2.975 |
pass |
| 910 |
annual_heating |
1.887 MWh |
1.560 to 2.300 |
1.971 |
pass |
| 910 |
annual_cooling |
1.615 MWh |
0.860 to 2.000 |
1.374 |
pass |
| 910 |
peak_heating |
2.676 kW |
2.329 to 2.939 |
2.648 |
pass |
| 910 |
peak_cooling |
2.280 kW |
1.945 to 2.858 |
2.305 |
pass |
| 920 |
annual_heating |
3.324 MWh |
2.550 to 4.200 |
3.326 |
pass |
| 920 |
annual_cooling |
2.663 MWh |
2.430 to 3.080 |
2.786 |
pass |
| 920 |
peak_heating |
2.743 kW |
2.367 to 3.040 |
2.710 |
pass |
| 920 |
peak_cooling |
3.223 kW |
2.536 to 3.655 |
3.127 |
pass |
| 930 |
annual_heating |
3.745 MWh |
2.750 to 5.350 |
4.064 |
pass |
| 930 |
annual_cooling |
2.177 MWh |
1.240 to 2.640 |
1.898 |
pass |
| 930 |
peak_heating |
2.753 kW |
2.389 to 3.116 |
2.751 |
pass |
| 930 |
peak_cooling |
2.869 kW |
2.182 to 3.205 |
2.656 |
pass |
| 940 |
annual_heating |
1.100 MWh |
0.220 to 1.910 |
1.109 |
pass |
| 940 |
annual_cooling |
2.329 MWh |
2.240 to 3.140 |
2.401 |
pass |
| 940 |
peak_heating |
3.274 kW |
2.858 to 4.076 |
3.377 |
pass |
| 940 |
peak_cooling |
2.974 kW |
2.387 to 3.545 |
2.993 |
pass |
| 950 |
annual_heating |
0.000 MWh |
0.000 to 0.000 |
0.000 |
pass |
| 950 |
annual_cooling |
0.717 MWh |
0.430 to 1.520 |
0.634 |
pass |
| 950 |
peak_heating |
0.000 kW |
0.000 to 0.000 |
0.000 |
pass |
| 950 |
peak_cooling |
2.385 kW |
1.935 to 2.507 |
2.268 |
pass |
| 960 |
annual_heating |
2.588 MWh |
2.000 to 3.400 |
2.693 |
pass |
| 960 |
annual_cooling |
0.950 MWh |
0.620 to 1.810 |
0.896 |
pass |
| 960 |
peak_heating |
2.104 kW |
1.970 to 2.415 |
2.195 |
pass |
| 960 |
peak_cooling |
1.475 kW |
1.264 to 1.554 |
1.393 |
pass |
| 960 |
maximum_temperature |
48.036 degC |
47.100 to 54.200 |
49.920 |
pass |
| 960 |
minimum_temperature |
4.160 degC |
3.200 to 9.000 |
5.800 |
pass |
| 960 |
mean_temperature |
26.693 degC |
25.800 to 30.500 |
28.060 |
pass |
| 980 |
annual_heating |
0.441 MWh |
-0.610 to 1.280 |
0.407 |
pass |
| 980 |
annual_cooling |
3.415 MWh |
3.520 to 4.490 |
3.710 |
known deviation: Buildings' own Case980 gives 3.418 MWh, 3 % below the lower limit of the standard (3.52 MWh); trano reproduces the library's model. |
| 980 |
peak_heating |
1.538 kW |
1.169 to 1.778 |
1.489 |
pass |
| 980 |
peak_cooling |
3.296 kW |
2.747 to 3.851 |
3.348 |
pass |
| 985 |
annual_heating |
2.371 MWh |
1.680 to 3.090 |
2.398 |
pass |
| 985 |
annual_cooling |
6.140 MWh |
5.950 to 7.260 |
6.351 |
pass |
| 985 |
peak_heating |
2.666 kW |
2.313 to 2.924 |
2.631 |
pass |
| 985 |
peak_cooling |
3.863 kW |
2.997 to 4.436 |
3.824 |
pass |
| 995 |
annual_heating |
0.984 MWh |
-0.150 to 2.020 |
0.974 |
pass |
| 995 |
annual_cooling |
6.789 MWh |
6.580 to 8.410 |
7.145 |
pass |
| 995 |
peak_heating |
1.598 kW |
1.284 to 1.797 |
1.565 |
pass |
| 995 |
peak_cooling |
3.973 kW |
3.104 to 4.435 |
3.986 |
pass |
| 600FF |
maximum_temperature |
63.318 degC |
61.400 to 69.400 |
64.600 |
pass |
| 600FF |
minimum_temperature |
-12.847 degC |
-14.800 to -8.900 |
-12.700 |
pass |
| 600FF |
mean_temperature |
24.664 degC |
23.300 to 27.100 |
25.250 |
pass |
| 650FF |
maximum_temperature |
62.135 degC |
60.100 to 67.800 |
63.067 |
pass |
| 650FF |
minimum_temperature |
-16.922 degC |
-18.800 to -15.700 |
-17.333 |
pass |
| 650FF |
mean_temperature |
18.733 degC |
16.600 to 19.900 |
18.300 |
pass |
| 680FF |
maximum_temperature |
68.913 degC |
68.800 to 79.500 |
73.017 |
pass |
| 680FF |
minimum_temperature |
-7.313 degC |
-9.100 to -4.700 |
-6.867 |
pass |
| 680FF |
mean_temperature |
30.137 degC |
29.200 to 34.300 |
31.850 |
pass |
| 900FF |
maximum_temperature |
43.840 degC |
42.300 to 47.000 |
44.583 |
pass |
| 900FF |
minimum_temperature |
1.107 degC |
-0.400 to 3.200 |
1.250 |
pass |
| 900FF |
mean_temperature |
24.932 degC |
23.500 to 26.700 |
25.233 |
pass |
| 950FF |
maximum_temperature |
36.790 degC |
35.100 to 38.100 |
36.583 |
pass |
| 950FF |
minimum_temperature |
-12.046 degC |
-14.400 to -11.500 |
-12.983 |
pass |
| 950FF |
mean_temperature |
15.243 degC |
13.400 to 16.000 |
14.733 |
pass |
| 980FF |
maximum_temperature |
48.664 degC |
47.500 to 53.800 |
50.500 |
pass |
| 980FF |
minimum_temperature |
9.634 degC |
6.300 to 13.500 |
10.350 |
pass |
| 980FF |
mean_temperature |
30.470 degC |
29.500 to 34.300 |
31.800 |
pass |
IDEAS
| Case |
KPI |
trano |
Band |
Reference mean |
Status |
| 600 |
annual_heating |
4.541 MWh |
3.750 to 4.980 |
4.213 |
pass |
| 600 |
annual_cooling |
6.265 MWh |
5.000 to 6.830 |
5.856 |
pass |
| 600 |
peak_heating |
3.314 kW |
2.852 to 3.527 |
3.183 |
pass |
| 600 |
peak_cooling |
6.545 kW |
5.098 to 6.805 |
6.024 |
pass |
| 620 |
annual_heating |
4.727 MWh |
3.670 to 5.380 |
4.413 |
pass |
| 620 |
annual_cooling |
4.235 MWh |
2.760 to 5.190 |
4.090 |
pass |
| 620 |
peak_heating |
3.373 kW |
2.869 to 3.554 |
3.186 |
pass |
| 620 |
peak_cooling |
4.908 kW |
3.715 to 5.037 |
4.526 |
pass |
| 640 |
annual_heating |
2.769 MWh |
1.580 to 3.760 |
2.612 |
pass |
| 640 |
annual_cooling |
6.009 MWh |
4.440 to 6.860 |
5.636 |
pass |
| 640 |
peak_heating |
4.370 kW |
3.806 to 4.891 |
4.369 |
pass |
| 640 |
peak_cooling |
6.491 kW |
5.044 to 6.750 |
5.973 |
pass |
| 650 |
annual_heating |
0.000 MWh |
0.000 to 0.000 |
0.000 |
pass |
| 650 |
annual_cooling |
5.067 MWh |
3.460 to 5.880 |
4.644 |
pass |
| 650 |
peak_heating |
0.000 kW |
0.000 to 0.000 |
0.000 |
pass |
| 650 |
peak_cooling |
6.324 kW |
4.731 to 6.604 |
5.813 |
pass |
| 660 |
annual_heating |
3.723 MWh |
2.680 to 4.820 |
3.713 |
pass |
| 660 |
annual_cooling |
3.438 MWh |
1.910 to 4.330 |
3.172 |
pass |
| 660 |
peak_heating |
2.759 kW |
2.472 to 3.103 |
2.801 |
pass |
| 660 |
peak_cooling |
3.873 kW |
3.146 to 4.130 |
3.565 |
pass |
| 670 |
annual_heating |
6.119 MWh |
4.000 to 7.960 |
5.681 |
pass |
| 670 |
annual_cooling |
6.683 MWh |
5.050 to 7.670 |
6.402 |
pass |
| 670 |
peak_heating |
4.166 kW |
3.444 to 4.432 |
3.943 |
pass |
| 670 |
peak_cooling |
6.899 kW |
5.493 to 7.271 |
6.445 |
pass |
| 680 |
annual_heating |
2.359 MWh |
1.210 to 3.080 |
2.056 |
pass |
| 680 |
annual_cooling |
6.642 MWh |
5.130 to 7.700 |
6.264 |
pass |
| 680 |
peak_heating |
2.144 kW |
1.672 to 2.232 |
1.984 |
pass |
| 680 |
peak_cooling |
6.964 kW |
5.408 to 7.404 |
6.446 |
pass |
| 685 |
annual_heating |
5.024 MWh |
4.080 to 5.750 |
4.762 |
pass |
| 685 |
annual_cooling |
9.271 MWh |
7.700 to 10.140 |
8.886 |
pass |
| 685 |
peak_heating |
3.329 kW |
2.863 to 3.543 |
3.183 |
pass |
| 685 |
peak_cooling |
7.282 kW |
5.713 to 7.517 |
6.743 |
pass |
| 695 |
annual_heating |
2.927 MWh |
1.700 to 3.810 |
2.656 |
pass |
| 695 |
annual_cooling |
9.316 MWh |
7.490 to 10.580 |
8.912 |
pass |
| 695 |
peak_heating |
2.185 kW |
1.688 to 2.245 |
2.001 |
pass |
| 695 |
peak_cooling |
7.527 kW |
5.855 to 7.918 |
6.979 |
pass |
| 900 |
annual_heating |
1.763 MWh |
1.040 to 2.280 |
1.627 |
pass |
| 900 |
annual_cooling |
2.599 MWh |
2.350 to 2.600 |
2.467 |
pass |
| 900 |
peak_heating |
2.765 kW |
2.304 to 2.917 |
2.591 |
pass |
| 900 |
peak_cooling |
3.171 kW |
2.387 to 3.545 |
2.975 |
pass |
| 920 |
annual_heating |
3.493 MWh |
2.550 to 4.200 |
3.326 |
pass |
| 920 |
annual_cooling |
2.820 MWh |
2.430 to 3.080 |
2.786 |
pass |
| 920 |
peak_heating |
2.861 kW |
2.367 to 3.040 |
2.710 |
pass |
| 920 |
peak_cooling |
3.388 kW |
2.536 to 3.655 |
3.127 |
pass |
| 940 |
annual_heating |
1.126 MWh |
0.220 to 1.910 |
1.109 |
pass |
| 940 |
annual_cooling |
2.524 MWh |
2.240 to 3.140 |
2.401 |
pass |
| 940 |
peak_heating |
3.253 kW |
2.858 to 4.076 |
3.377 |
pass |
| 940 |
peak_cooling |
3.170 kW |
2.387 to 3.545 |
2.993 |
pass |
| 950 |
annual_heating |
0.000 MWh |
0.000 to 0.000 |
0.000 |
pass |
| 950 |
annual_cooling |
0.741 MWh |
0.430 to 1.520 |
0.634 |
pass |
| 950 |
peak_heating |
0.000 kW |
0.000 to 0.000 |
0.000 |
pass |
| 950 |
peak_cooling |
2.519 kW |
1.935 to 2.507 |
2.268 |
known deviation: 2.519 kW against a band ending at 2.507 kW (the spread of the reference programs plus 5 % of the largest peak): 0.4 % above a tolerance that is a convention, not a limit of the standard. |
| 960 |
annual_heating |
2.695 MWh |
2.000 to 3.400 |
2.693 |
pass |
| 960 |
annual_cooling |
0.950 MWh |
0.620 to 1.810 |
0.896 |
pass |
| 960 |
peak_heating |
2.217 kW |
1.970 to 2.415 |
2.195 |
pass |
| 960 |
peak_cooling |
1.510 kW |
1.264 to 1.554 |
1.393 |
pass |
| 960 |
maximum_temperature |
51.310 degC |
47.100 to 54.200 |
49.920 |
pass |
| 960 |
minimum_temperature |
4.133 degC |
3.200 to 9.000 |
5.800 |
pass |
| 960 |
mean_temperature |
28.027 degC |
25.800 to 30.500 |
28.060 |
pass |
| 980 |
annual_heating |
0.480 MWh |
-0.610 to 1.280 |
0.407 |
pass |
| 980 |
annual_cooling |
3.798 MWh |
3.520 to 4.490 |
3.710 |
pass |
| 980 |
peak_heating |
1.663 kW |
1.169 to 1.778 |
1.489 |
pass |
| 980 |
peak_cooling |
3.607 kW |
2.747 to 3.851 |
3.348 |
pass |
| 985 |
annual_heating |
2.464 MWh |
1.680 to 3.090 |
2.398 |
pass |
| 985 |
annual_cooling |
6.474 MWh |
5.950 to 7.260 |
6.351 |
pass |
| 985 |
peak_heating |
2.763 kW |
2.313 to 2.924 |
2.631 |
pass |
| 985 |
peak_cooling |
4.025 kW |
2.997 to 4.436 |
3.824 |
pass |
| 995 |
annual_heating |
1.063 MWh |
-0.150 to 2.020 |
0.974 |
pass |
| 995 |
annual_cooling |
7.272 MWh |
6.580 to 8.410 |
7.145 |
pass |
| 995 |
peak_heating |
1.715 kW |
1.284 to 1.797 |
1.565 |
pass |
| 995 |
peak_cooling |
4.257 kW |
3.104 to 4.435 |
3.986 |
pass |
| 600FF |
maximum_temperature |
66.086 degC |
61.400 to 69.400 |
64.600 |
pass |
| 600FF |
minimum_temperature |
-13.193 degC |
-14.800 to -8.900 |
-12.700 |
pass |
| 600FF |
mean_temperature |
25.109 degC |
23.300 to 27.100 |
25.250 |
pass |
| 650FF |
maximum_temperature |
64.789 degC |
60.100 to 67.800 |
63.067 |
pass |
| 650FF |
minimum_temperature |
-16.889 degC |
-18.800 to -15.700 |
-17.333 |
pass |
| 650FF |
mean_temperature |
18.996 degC |
16.600 to 19.900 |
18.300 |
pass |
| 680FF |
maximum_temperature |
72.328 degC |
68.800 to 79.500 |
73.017 |
pass |
| 680FF |
minimum_temperature |
-8.063 degC |
-9.100 to -4.700 |
-6.867 |
pass |
| 680FF |
mean_temperature |
30.991 degC |
29.200 to 34.300 |
31.850 |
pass |
| 900FF |
maximum_temperature |
44.753 degC |
42.300 to 47.000 |
44.583 |
pass |
| 900FF |
minimum_temperature |
0.814 degC |
-0.400 to 3.200 |
1.250 |
pass |
| 900FF |
mean_temperature |
25.256 degC |
23.500 to 26.700 |
25.233 |
pass |
| 950FF |
maximum_temperature |
37.197 degC |
35.100 to 38.100 |
36.583 |
pass |
| 950FF |
minimum_temperature |
-12.061 degC |
-14.400 to -11.500 |
-12.983 |
pass |
| 950FF |
mean_temperature |
15.341 degC |
13.400 to 16.000 |
14.733 |
pass |
| 980FF |
maximum_temperature |
50.242 degC |
47.500 to 53.800 |
50.500 |
pass |
| 980FF |
minimum_temperature |
9.351 degC |
6.300 to 13.500 |
10.350 |
pass |
| 980FF |
mean_temperature |
31.131 degC |
29.500 to 34.300 |
31.800 |
pass |
iso_13790
| Case |
KPI |
trano |
Band |
Reference mean |
Status |
| 600 |
annual_heating |
3.122 MWh |
3.750 to 4.980 |
4.213 |
fail |
| 600 |
annual_cooling |
5.298 MWh |
5.000 to 6.830 |
5.856 |
pass |
| 600 |
peak_heating |
3.099 kW |
2.852 to 3.527 |
3.183 |
pass |
| 600 |
peak_cooling |
4.870 kW |
5.098 to 6.805 |
6.024 |
fail |
| 620 |
annual_heating |
3.920 MWh |
3.670 to 5.380 |
4.413 |
pass |
| 620 |
annual_cooling |
3.777 MWh |
2.760 to 5.190 |
4.090 |
pass |
| 620 |
peak_heating |
3.112 kW |
2.869 to 3.554 |
3.186 |
pass |
| 620 |
peak_cooling |
4.328 kW |
3.715 to 5.037 |
4.526 |
pass |
| 640 |
annual_heating |
1.879 MWh |
1.580 to 3.760 |
2.612 |
pass |
| 640 |
annual_cooling |
4.942 MWh |
4.440 to 6.860 |
5.636 |
pass |
| 640 |
peak_heating |
4.350 kW |
3.806 to 4.891 |
4.369 |
pass |
| 640 |
peak_cooling |
4.870 kW |
5.044 to 6.750 |
5.973 |
fail |
| 660 |
annual_heating |
2.660 MWh |
2.680 to 4.820 |
3.713 |
fail |
| 660 |
annual_cooling |
2.612 MWh |
1.910 to 4.330 |
3.172 |
pass |
| 660 |
peak_heating |
2.557 kW |
2.472 to 3.103 |
2.801 |
pass |
| 660 |
peak_cooling |
3.078 kW |
3.146 to 4.130 |
3.565 |
fail |
| 670 |
annual_heating |
5.029 MWh |
4.000 to 7.960 |
5.681 |
pass |
| 670 |
annual_cooling |
4.901 MWh |
5.050 to 7.670 |
6.402 |
fail |
| 670 |
peak_heating |
4.045 kW |
3.444 to 4.432 |
3.943 |
pass |
| 670 |
peak_cooling |
5.015 kW |
5.493 to 7.271 |
6.445 |
fail |
| 680 |
annual_heating |
1.242 MWh |
1.210 to 3.080 |
2.056 |
pass |
| 680 |
annual_cooling |
6.451 MWh |
5.130 to 7.700 |
6.264 |
pass |
| 680 |
peak_heating |
2.096 kW |
1.672 to 2.232 |
1.984 |
pass |
| 680 |
peak_cooling |
5.138 kW |
5.408 to 7.404 |
6.446 |
fail |
| 685 |
annual_heating |
4.137 MWh |
4.080 to 5.750 |
4.762 |
pass |
| 685 |
annual_cooling |
9.344 MWh |
7.700 to 10.140 |
8.886 |
pass |
| 685 |
peak_heating |
3.090 kW |
2.863 to 3.543 |
3.183 |
pass |
| 685 |
peak_cooling |
5.754 kW |
5.713 to 7.517 |
6.743 |
pass |
| 695 |
annual_heating |
2.256 MWh |
1.700 to 3.810 |
2.656 |
pass |
| 695 |
annual_cooling |
10.030 MWh |
7.490 to 10.580 |
8.912 |
pass |
| 695 |
peak_heating |
2.090 kW |
1.688 to 2.245 |
2.001 |
pass |
| 695 |
peak_cooling |
6.030 kW |
5.855 to 7.918 |
6.979 |
pass |
| 900 |
annual_heating |
1.803 MWh |
1.040 to 2.280 |
1.627 |
pass |
| 900 |
annual_cooling |
3.581 MWh |
2.350 to 2.600 |
2.467 |
fail |
| 900 |
peak_heating |
2.880 kW |
2.304 to 2.917 |
2.591 |
pass |
| 900 |
peak_cooling |
3.532 kW |
2.387 to 3.545 |
2.975 |
pass |
| 920 |
annual_heating |
3.440 MWh |
2.550 to 4.200 |
3.326 |
pass |
| 920 |
annual_cooling |
3.264 MWh |
2.430 to 3.080 |
2.786 |
fail |
| 920 |
peak_heating |
2.933 kW |
2.367 to 3.040 |
2.710 |
pass |
| 920 |
peak_cooling |
3.535 kW |
2.536 to 3.655 |
3.127 |
pass |
| 940 |
annual_heating |
1.276 MWh |
0.220 to 1.910 |
1.109 |
pass |
| 940 |
annual_cooling |
3.498 MWh |
2.240 to 3.140 |
2.401 |
fail |
| 940 |
peak_heating |
4.156 kW |
2.858 to 4.076 |
3.377 |
fail |
| 940 |
peak_cooling |
3.531 kW |
2.387 to 3.545 |
2.993 |
pass |
| 980 |
annual_heating |
0.532 MWh |
-0.610 to 1.280 |
0.407 |
pass |
| 980 |
annual_cooling |
5.255 MWh |
3.520 to 4.490 |
3.710 |
fail |
| 980 |
peak_heating |
1.886 kW |
1.169 to 1.778 |
1.489 |
fail |
| 980 |
peak_cooling |
3.733 kW |
2.747 to 3.851 |
3.348 |
pass |
| 985 |
annual_heating |
2.730 MWh |
1.680 to 3.090 |
2.398 |
pass |
| 985 |
annual_cooling |
7.937 MWh |
5.950 to 7.260 |
6.351 |
fail |
| 985 |
peak_heating |
2.871 kW |
2.313 to 2.924 |
2.631 |
pass |
| 985 |
peak_cooling |
4.204 kW |
2.997 to 4.436 |
3.824 |
pass |
| 995 |
annual_heating |
1.195 MWh |
-0.150 to 2.020 |
0.974 |
pass |
| 995 |
annual_cooling |
8.954 MWh |
6.580 to 8.410 |
7.145 |
fail |
| 995 |
peak_heating |
1.886 kW |
1.284 to 1.797 |
1.565 |
fail |
| 995 |
peak_cooling |
4.228 kW |
3.104 to 4.435 |
3.986 |
pass |
| 600FF |
maximum_temperature |
54.174 degC |
61.400 to 69.400 |
64.600 |
fail |
| 600FF |
minimum_temperature |
-7.447 degC |
-14.800 to -8.900 |
-12.700 |
fail |
| 600FF |
mean_temperature |
26.564 degC |
23.300 to 27.100 |
25.250 |
pass |
| 680FF |
maximum_temperature |
61.503 degC |
68.800 to 79.500 |
73.017 |
fail |
| 680FF |
minimum_temperature |
-0.611 degC |
-9.100 to -4.700 |
-6.867 |
fail |
| 680FF |
mean_temperature |
33.913 degC |
29.200 to 34.300 |
31.850 |
pass |
| 900FF |
maximum_temperature |
47.038 degC |
42.300 to 47.000 |
44.583 |
fail |
| 900FF |
minimum_temperature |
0.045 degC |
-0.400 to 3.200 |
1.250 |
pass |
| 900FF |
mean_temperature |
26.610 degC |
23.500 to 26.700 |
25.233 |
pass |
| 980FF |
maximum_temperature |
54.832 degC |
47.500 to 53.800 |
50.500 |
fail |
| 980FF |
minimum_temperature |
8.231 degC |
6.300 to 13.500 |
10.350 |
pass |
| 980FF |
mean_temperature |
33.914 degC |
29.500 to 34.300 |
31.800 |
pass |
reduced_order
| Case |
KPI |
trano |
Band |
Reference mean |
Status |
| 600 |
annual_heating |
5.873 MWh |
3.750 to 4.980 |
4.213 |
fail |
| 600 |
annual_cooling |
3.883 MWh |
5.000 to 6.830 |
5.856 |
fail |
| 600 |
peak_heating |
3.731 kW |
2.852 to 3.527 |
3.183 |
fail |
| 600 |
peak_cooling |
4.113 kW |
5.098 to 6.805 |
6.024 |
fail |
| 620 |
annual_heating |
6.058 MWh |
3.670 to 5.380 |
4.413 |
fail |
| 620 |
annual_cooling |
2.786 MWh |
2.760 to 5.190 |
4.090 |
pass |
| 620 |
peak_heating |
3.731 kW |
2.869 to 3.554 |
3.186 |
fail |
| 620 |
peak_cooling |
3.926 kW |
3.715 to 5.037 |
4.526 |
pass |
| 640 |
annual_heating |
3.765 MWh |
1.580 to 3.760 |
2.612 |
fail |
| 640 |
annual_cooling |
3.791 MWh |
4.440 to 6.860 |
5.636 |
fail |
| 640 |
peak_heating |
3.445 kW |
3.806 to 4.891 |
4.369 |
fail |
| 640 |
peak_cooling |
4.103 kW |
5.044 to 6.750 |
5.973 |
fail |
| 660 |
annual_heating |
4.580 MWh |
2.680 to 4.820 |
3.713 |
pass |
| 660 |
annual_cooling |
2.249 MWh |
1.910 to 4.330 |
3.172 |
pass |
| 660 |
peak_heating |
2.956 kW |
2.472 to 3.103 |
2.801 |
pass |
| 660 |
peak_cooling |
2.614 kW |
3.146 to 4.130 |
3.565 |
fail |
| 670 |
annual_heating |
10.069 MWh |
4.000 to 7.960 |
5.681 |
fail |
| 670 |
annual_cooling |
2.934 MWh |
5.050 to 7.670 |
6.402 |
fail |
| 670 |
peak_heating |
5.726 kW |
3.444 to 4.432 |
3.943 |
fail |
| 670 |
peak_cooling |
4.186 kW |
5.493 to 7.271 |
6.445 |
fail |
| 680 |
annual_heating |
3.726 MWh |
1.210 to 3.080 |
2.056 |
fail |
| 680 |
annual_cooling |
4.529 MWh |
5.130 to 7.700 |
6.264 |
fail |
| 680 |
peak_heating |
2.603 kW |
1.672 to 2.232 |
1.984 |
fail |
| 680 |
peak_cooling |
4.501 kW |
5.408 to 7.404 |
6.446 |
fail |
| 685 |
annual_heating |
5.970 MWh |
4.080 to 5.750 |
4.762 |
fail |
| 685 |
annual_cooling |
6.378 MWh |
7.700 to 10.140 |
8.886 |
fail |
| 685 |
peak_heating |
3.714 kW |
2.863 to 3.543 |
3.183 |
fail |
| 685 |
peak_cooling |
4.846 kW |
5.713 to 7.517 |
6.743 |
fail |
| 695 |
annual_heating |
3.811 MWh |
1.700 to 3.810 |
2.656 |
fail |
| 695 |
annual_cooling |
6.549 MWh |
7.490 to 10.580 |
8.912 |
fail |
| 695 |
peak_heating |
2.590 kW |
1.688 to 2.245 |
2.001 |
fail |
| 695 |
peak_cooling |
5.054 kW |
5.855 to 7.918 |
6.979 |
fail |
| 900 |
annual_heating |
5.263 MWh |
1.040 to 2.280 |
1.627 |
fail |
| 900 |
annual_cooling |
3.184 MWh |
2.350 to 2.600 |
2.467 |
fail |
| 900 |
peak_heating |
3.726 kW |
2.304 to 2.917 |
2.591 |
fail |
| 900 |
peak_cooling |
3.631 kW |
2.387 to 3.545 |
2.975 |
fail |
| 920 |
annual_heating |
5.632 MWh |
2.550 to 4.200 |
3.326 |
fail |
| 920 |
annual_cooling |
2.343 MWh |
2.430 to 3.080 |
2.786 |
fail |
| 920 |
peak_heating |
3.726 kW |
2.367 to 3.040 |
2.710 |
fail |
| 920 |
peak_cooling |
3.492 kW |
2.536 to 3.655 |
3.127 |
pass |
| 940 |
annual_heating |
3.321 MWh |
0.220 to 1.910 |
1.109 |
fail |
| 940 |
annual_cooling |
3.059 MWh |
2.240 to 3.140 |
2.401 |
pass |
| 940 |
peak_heating |
3.187 kW |
2.858 to 4.076 |
3.377 |
pass |
| 940 |
peak_cooling |
3.611 kW |
2.387 to 3.545 |
2.993 |
fail |
| 980 |
annual_heating |
3.665 MWh |
-0.610 to 1.280 |
0.407 |
fail |
| 980 |
annual_cooling |
4.460 MWh |
3.520 to 4.490 |
3.710 |
pass |
| 980 |
peak_heating |
2.603 kW |
1.169 to 1.778 |
1.489 |
fail |
| 980 |
peak_cooling |
4.444 kW |
2.747 to 3.851 |
3.348 |
fail |
| 985 |
annual_heating |
5.444 MWh |
1.680 to 3.090 |
2.398 |
fail |
| 985 |
annual_cooling |
5.848 MWh |
5.950 to 7.260 |
6.351 |
fail |
| 985 |
peak_heating |
3.709 kW |
2.313 to 2.924 |
2.631 |
fail |
| 985 |
peak_cooling |
4.414 kW |
2.997 to 4.436 |
3.824 |
pass |
| 995 |
annual_heating |
3.763 MWh |
-0.150 to 2.020 |
0.974 |
fail |
| 995 |
annual_cooling |
6.487 MWh |
6.580 to 8.410 |
7.145 |
fail |
| 995 |
peak_heating |
2.590 kW |
1.284 to 1.797 |
1.565 |
fail |
| 995 |
peak_cooling |
5.006 kW |
3.104 to 4.435 |
3.986 |
fail |
| 600FF |
maximum_temperature |
62.110 degC |
61.400 to 69.400 |
64.600 |
pass |
| 600FF |
minimum_temperature |
-14.177 degC |
-14.800 to -8.900 |
-12.700 |
pass |
| 600FF |
mean_temperature |
20.451 degC |
23.300 to 27.100 |
25.250 |
fail |
| 680FF |
maximum_temperature |
78.794 degC |
68.800 to 79.500 |
73.017 |
pass |
| 680FF |
minimum_temperature |
-11.117 degC |
-9.100 to -4.700 |
-6.867 |
fail |
| 680FF |
mean_temperature |
24.262 degC |
29.200 to 34.300 |
31.850 |
fail |
| 900FF |
maximum_temperature |
56.089 degC |
42.300 to 47.000 |
44.583 |
fail |
| 900FF |
minimum_temperature |
-10.040 degC |
-0.400 to 3.200 |
1.250 |
fail |
| 900FF |
mean_temperature |
20.461 degC |
23.500 to 26.700 |
25.233 |
fail |
| 980FF |
maximum_temperature |
77.475 degC |
47.500 to 53.800 |
50.500 |
fail |
| 980FF |
minimum_temperature |
-9.062 degC |
6.300 to 13.500 |
10.350 |
fail |
| 980FF |
mean_temperature |
24.248 degC |
29.500 to 34.300 |
31.800 |
fail |
FastSmoothBuildings
The FastSmoothBuildings library is trano's reduced model of the same building: the closed-loop model whose components
rumoca translates to a CasADi ODE for optimal control and calibration. It runs the same YAML files in OpenModelica.
Its walls are discretised as Buildings discretises them (number_of_states, at most three sublayers per layer), its
zones take the air density of the site and exchange long-wave radiation as the YAML asks (linearised at 20 degC or
around the current surface temperatures), its outer surfaces exchange with sky and ground exactly, the gas gaps of its
glazings conduct at the temperatures of their panes (long-wave exchange and convection of the gas, as Buildings), its
windows are shaded by overhangs and side fins as in Buildings, and its controllers are smooth and without events. It
gates as Buildings and IDEAS do, on the 27 cases. The column Buildings gives the frozen value of Buildings for the
same case (expected/Buildings.json), so that the gap between the two libraries reads next to the band. How the two
libraries compare hour by hour, and how they respond to a change of the parameters, is studied in the
documentation of FastSmoothBuildings; how the library came to these results is told in its
improvement plan.
105 of 105 KPIs of 27 cases are inside their band.
Against Buildings, the loads differ by 1.1 % on average and 4.4 % at most, the temperatures of the free-floating zones by 0.38 K on average and 1.70 K at most.
| Case |
KPI |
FastSmoothBuildings |
Buildings |
Band |
Reference mean |
Status |
| 600 |
annual_heating |
4.463 MWh |
4.449 MWh |
3.750 to 4.980 |
4.213 |
pass |
| 600 |
annual_cooling |
6.051 MWh |
5.973 MWh |
5.000 to 6.830 |
5.856 |
pass |
| 600 |
peak_heating |
3.222 kW |
3.215 kW |
2.852 to 3.527 |
3.183 |
pass |
| 600 |
peak_cooling |
6.262 kW |
6.187 kW |
5.098 to 6.805 |
6.024 |
pass |
| 610 |
annual_heating |
4.489 MWh |
4.475 MWh |
3.610 to 5.270 |
4.311 |
pass |
| 610 |
annual_cooling |
4.864 MWh |
4.810 MWh |
2.740 to 6.030 |
4.256 |
pass |
| 610 |
peak_heating |
3.222 kW |
3.216 kW |
2.853 to 3.528 |
3.168 |
pass |
| 610 |
peak_cooling |
6.140 kW |
6.082 kW |
5.009 to 6.754 |
5.861 |
pass |
| 620 |
annual_heating |
4.580 MWh |
4.563 MWh |
3.670 to 5.380 |
4.413 |
pass |
| 620 |
annual_cooling |
4.110 MWh |
4.087 MWh |
2.760 to 5.190 |
4.090 |
pass |
| 620 |
peak_heating |
3.255 kW |
3.248 kW |
2.869 to 3.554 |
3.186 |
pass |
| 620 |
peak_cooling |
4.724 kW |
4.700 kW |
3.715 to 5.037 |
4.526 |
pass |
| 630 |
annual_heating |
4.771 MWh |
4.746 MWh |
3.690 to 6.120 |
4.822 |
pass |
| 630 |
annual_cooling |
3.328 MWh |
3.320 MWh |
1.080 to 4.420 |
2.814 |
pass |
| 630 |
peak_heating |
3.258 kW |
3.251 kW |
2.870 to 3.557 |
3.203 |
pass |
| 630 |
peak_cooling |
4.267 kW |
4.250 kW |
3.315 to 4.423 |
3.963 |
pass |
| 640 |
annual_heating |
2.724 MWh |
2.716 MWh |
1.580 to 3.760 |
2.612 |
pass |
| 640 |
annual_cooling |
5.799 MWh |
5.725 MWh |
4.440 to 6.860 |
5.636 |
pass |
| 640 |
peak_heating |
4.345 kW |
4.356 kW |
3.806 to 4.891 |
4.369 |
pass |
| 640 |
peak_cooling |
6.211 kW |
6.138 kW |
5.044 to 6.750 |
5.973 |
pass |
| 650 |
annual_heating |
0.000 MWh |
0.000 MWh |
0.000 to 0.000 |
0.000 |
pass |
| 650 |
annual_cooling |
4.871 MWh |
4.802 MWh |
3.460 to 5.880 |
4.644 |
pass |
| 650 |
peak_heating |
0.000 kW |
0.000 kW |
0.000 to 0.000 |
0.000 |
pass |
| 650 |
peak_cooling |
6.036 kW |
5.949 kW |
4.731 to 6.604 |
5.813 |
pass |
| 660 |
annual_heating |
3.610 MWh |
3.620 MWh |
2.680 to 4.820 |
3.713 |
pass |
| 660 |
annual_cooling |
3.407 MWh |
3.315 MWh |
1.910 to 4.330 |
3.172 |
pass |
| 660 |
peak_heating |
2.722 kW |
2.728 kW |
2.472 to 3.103 |
2.801 |
pass |
| 660 |
peak_cooling |
3.719 kW |
3.629 kW |
3.146 to 4.130 |
3.565 |
pass |
| 670 |
annual_heating |
6.632 MWh |
6.473 MWh |
4.000 to 7.960 |
5.681 |
pass |
| 670 |
annual_cooling |
6.223 MWh |
6.361 MWh |
5.050 to 7.670 |
6.402 |
pass |
| 670 |
peak_heating |
4.402 kW |
4.294 kW |
3.444 to 4.432 |
3.943 |
pass |
| 670 |
peak_cooling |
6.518 kW |
6.560 kW |
5.493 to 7.271 |
6.445 |
pass |
| 680 |
annual_heating |
2.237 MWh |
2.227 MWh |
1.210 to 3.080 |
2.056 |
pass |
| 680 |
annual_cooling |
6.316 MWh |
6.136 MWh |
5.130 to 7.700 |
6.264 |
pass |
| 680 |
peak_heating |
2.032 kW |
2.013 kW |
1.672 to 2.232 |
1.984 |
pass |
| 680 |
peak_cooling |
6.637 kW |
6.518 kW |
5.408 to 7.404 |
6.446 |
pass |
| 685 |
annual_heating |
4.945 MWh |
4.932 MWh |
4.080 to 5.750 |
4.763 |
pass |
| 685 |
annual_cooling |
9.030 MWh |
8.946 MWh |
7.700 to 10.140 |
8.886 |
pass |
| 685 |
peak_heating |
3.233 kW |
3.225 kW |
2.863 to 3.543 |
3.183 |
pass |
| 685 |
peak_cooling |
7.010 kW |
6.932 kW |
5.713 to 7.517 |
6.743 |
pass |
| 695 |
annual_heating |
2.781 MWh |
2.768 MWh |
1.700 to 3.810 |
2.656 |
pass |
| 695 |
annual_cooling |
8.946 MWh |
8.754 MWh |
7.490 to 10.580 |
8.912 |
pass |
| 695 |
peak_heating |
2.056 kW |
2.047 kW |
1.688 to 2.245 |
2.001 |
pass |
| 695 |
peak_cooling |
7.203 kW |
7.080 kW |
5.855 to 7.918 |
6.979 |
pass |
| 900 |
annual_heating |
1.712 MWh |
1.718 MWh |
1.040 to 2.280 |
1.627 |
pass |
| 900 |
annual_cooling |
2.440 MWh |
2.395 MWh |
2.350 to 2.600 |
2.467 |
pass |
| 900 |
peak_heating |
2.690 kW |
2.668 kW |
2.304 to 2.917 |
2.591 |
pass |
| 900 |
peak_cooling |
3.039 kW |
2.974 kW |
2.387 to 3.545 |
2.975 |
pass |
| 910 |
annual_heating |
1.882 MWh |
1.887 MWh |
1.560 to 2.300 |
1.971 |
pass |
| 910 |
annual_cooling |
1.637 MWh |
1.615 MWh |
0.860 to 2.000 |
1.374 |
pass |
| 910 |
peak_heating |
2.698 kW |
2.676 kW |
2.329 to 2.939 |
2.648 |
pass |
| 910 |
peak_cooling |
2.330 kW |
2.280 kW |
1.945 to 2.858 |
2.305 |
pass |
| 920 |
annual_heating |
3.348 MWh |
3.324 MWh |
2.550 to 4.200 |
3.326 |
pass |
| 920 |
annual_cooling |
2.693 MWh |
2.663 MWh |
2.430 to 3.080 |
2.786 |
pass |
| 920 |
peak_heating |
2.762 kW |
2.743 kW |
2.367 to 3.040 |
2.710 |
pass |
| 920 |
peak_cooling |
3.245 kW |
3.223 kW |
2.536 to 3.655 |
3.127 |
pass |
| 930 |
annual_heating |
3.779 MWh |
3.745 MWh |
2.750 to 5.350 |
4.064 |
pass |
| 930 |
annual_cooling |
2.194 MWh |
2.177 MWh |
1.240 to 2.640 |
1.898 |
pass |
| 930 |
peak_heating |
2.774 kW |
2.753 kW |
2.389 to 3.116 |
2.751 |
pass |
| 930 |
peak_cooling |
2.883 kW |
2.869 kW |
2.182 to 3.205 |
2.656 |
pass |
| 940 |
annual_heating |
1.096 MWh |
1.101 MWh |
0.220 to 1.910 |
1.109 |
pass |
| 940 |
annual_cooling |
2.370 MWh |
2.329 MWh |
2.240 to 3.140 |
2.401 |
pass |
| 940 |
peak_heating |
3.301 kW |
3.274 kW |
2.858 to 4.076 |
3.377 |
pass |
| 940 |
peak_cooling |
3.038 kW |
2.974 kW |
2.387 to 3.545 |
2.993 |
pass |
| 950 |
annual_heating |
0.000 MWh |
0.000 MWh |
0.000 to 0.000 |
0.000 |
pass |
| 950 |
annual_cooling |
0.727 MWh |
0.717 MWh |
0.430 to 1.520 |
0.634 |
pass |
| 950 |
peak_heating |
0.000 kW |
0.000 kW |
0.000 to 0.000 |
0.000 |
pass |
| 950 |
peak_cooling |
2.395 kW |
2.385 kW |
1.935 to 2.507 |
2.268 |
pass |
| 960 |
annual_heating |
2.575 MWh |
2.588 MWh |
2.000 to 3.400 |
2.693 |
pass |
| 960 |
annual_cooling |
0.928 MWh |
0.950 MWh |
0.620 to 1.810 |
0.896 |
pass |
| 960 |
peak_heating |
2.108 kW |
2.104 kW |
1.970 to 2.415 |
2.195 |
pass |
| 960 |
peak_cooling |
1.424 kW |
1.476 kW |
1.264 to 1.554 |
1.393 |
pass |
| 960 |
maximum_temperature |
49.050 degC |
48.036 degC |
47.100 to 54.200 |
49.920 |
pass |
| 960 |
minimum_temperature |
4.204 degC |
4.160 degC |
3.200 to 9.000 |
5.800 |
pass |
| 960 |
mean_temperature |
27.112 degC |
26.693 degC |
25.800 to 30.500 |
28.060 |
pass |
| 980 |
annual_heating |
0.437 MWh |
0.441 MWh |
-0.610 to 1.280 |
0.407 |
pass |
| 980 |
annual_cooling |
3.567 MWh |
3.415 MWh |
3.520 to 4.490 |
3.710 |
pass |
| 980 |
peak_heating |
1.554 kW |
1.538 kW |
1.169 to 1.778 |
1.489 |
pass |
| 980 |
peak_cooling |
3.404 kW |
3.296 kW |
2.747 to 3.851 |
3.348 |
pass |
| 985 |
annual_heating |
2.376 MWh |
2.371 MWh |
1.680 to 3.090 |
2.398 |
pass |
| 985 |
annual_cooling |
6.211 MWh |
6.140 MWh |
5.950 to 7.260 |
6.351 |
pass |
| 985 |
peak_heating |
2.688 kW |
2.666 kW |
2.313 to 2.924 |
2.631 |
pass |
| 985 |
peak_cooling |
3.939 kW |
3.863 kW |
2.997 to 4.436 |
3.824 |
pass |
| 995 |
annual_heating |
0.982 MWh |
0.984 MWh |
-0.150 to 2.020 |
0.974 |
pass |
| 995 |
annual_cooling |
6.958 MWh |
6.789 MWh |
6.580 to 8.410 |
7.145 |
pass |
| 995 |
peak_heating |
1.615 kW |
1.598 kW |
1.284 to 1.797 |
1.565 |
pass |
| 995 |
peak_cooling |
4.061 kW |
3.973 kW |
3.104 to 4.435 |
3.986 |
pass |
| 600FF |
maximum_temperature |
64.382 degC |
63.318 degC |
61.400 to 69.400 |
64.600 |
pass |
| 600FF |
minimum_temperature |
-12.974 degC |
-12.847 degC |
-14.800 to -8.900 |
-12.700 |
pass |
| 600FF |
mean_temperature |
24.811 degC |
24.664 degC |
23.300 to 27.100 |
25.250 |
pass |
| 650FF |
maximum_temperature |
63.173 degC |
62.135 degC |
60.100 to 67.800 |
63.067 |
pass |
| 650FF |
minimum_temperature |
-16.901 degC |
-16.922 degC |
-18.800 to -15.700 |
-17.333 |
pass |
| 650FF |
mean_temperature |
18.859 degC |
18.733 degC |
16.600 to 19.900 |
18.300 |
pass |
| 680FF |
maximum_temperature |
70.617 degC |
68.913 degC |
68.800 to 79.500 |
73.017 |
pass |
| 680FF |
minimum_temperature |
-7.515 degC |
-7.312 degC |
-9.100 to -4.700 |
-6.867 |
pass |
| 680FF |
mean_temperature |
30.546 degC |
30.137 degC |
29.200 to 34.300 |
31.850 |
pass |
| 900FF |
maximum_temperature |
44.071 degC |
43.840 degC |
42.300 to 47.000 |
44.583 |
pass |
| 900FF |
minimum_temperature |
0.977 degC |
1.107 degC |
-0.400 to 3.200 |
1.250 |
pass |
| 900FF |
mean_temperature |
25.033 degC |
24.932 degC |
23.500 to 26.700 |
25.233 |
pass |
| 950FF |
maximum_temperature |
36.930 degC |
36.790 degC |
35.100 to 38.100 |
36.583 |
pass |
| 950FF |
minimum_temperature |
-12.060 degC |
-12.046 degC |
-14.400 to -11.500 |
-12.983 |
pass |
| 950FF |
mean_temperature |
15.292 degC |
15.243 degC |
13.400 to 16.000 |
14.733 |
pass |
| 980FF |
maximum_temperature |
49.339 degC |
48.664 degC |
47.500 to 53.800 |
50.500 |
pass |
| 980FF |
minimum_temperature |
9.628 degC |
9.634 degC |
6.300 to 13.500 |
10.350 |
pass |
| 980FF |
mean_temperature |
30.839 degC |
30.470 degC |
29.500 to 34.300 |
31.800 |
pass |