Skip to content

Parameters

Every parameter is optional: a parameter left out of the YAML is not written to the Modelica model, so the library's own default applies ("library default" below), unless trano has a default of its own. The library columns give the Modelica name the parameter is rendered under; a dash means the library does not take it (a value given anyway is ignored with a warning). numerical marks simulation settings rather than physical properties. The page is generated from trano/data_models/parameters.yaml.

AhuParameters

Elements: airhandlingunit

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
m_flow_nominal Nominal mass flow rate [kg/s] 2*100*1.2/3600 mAir_flow_nominal (when given; default variant); m_flow_nominal (test, system_d, system_c variant) mAir_flow_nominal (when given; default variant); m_flow_nominal (test, system_d, system_c variant) mAir_flow_nominal (when given; default variant); m_flow_nominal (test, system_d, system_c variant) mAir_flow_nominal (when given; default variant); m_flow_nominal (test, system_d, system_c variant)
dp_nominal Nominal pressure raise [Pa] 200 dp_nominal (test, system_d, system_c variant) dp_nominal (test, system_d, system_c variant) dp_nominal (test, system_d, system_c variant) dp_nominal (test, system_d, system_c variant)
heat_exchanger_effectiveness Heat exchanger effectiveness [1] 0.8 eps (test, system_d variant) eps (test, system_d variant) eps (test, system_d variant) eps (test, system_d variant)
supply_dp_nominal Pressure rise of the supply fan [Pa], the nominal pressure rise by default library default dpSup_nominal (test, system_d variant) dpSup_nominal (test, system_d variant) dpSup_nominal (test, system_d variant) dpSup_nominal (test, system_d variant)
return_dp_nominal Pressure rise of the return fan [Pa], the nominal pressure rise by default library default dpRet_nominal (test, system_d variant) dpRet_nominal (test, system_d variant) dpRet_nominal (test, system_d variant) dpRet_nominal (test, system_d variant)
building_static_pressure Static pressure of the building the supply fan maintains [Pa], 12 by default (default variant) library default dpBuiStaSet (default variant) dpBuiStaSet (default variant) dpBuiStaSet (default variant) dpBuiStaSet (default variant)
outdoor_air_per_area Outdoor air flow per floor area [m3/(s.m2)], 0.3e-3 by default (default variant, ASHRAE 62.1) library default ratOAFlo_A (default variant) ratOAFlo_A (default variant) ratOAFlo_A (default variant) ratOAFlo_A (default variant)
outdoor_air_per_person Outdoor air flow per person [m3/s], 2.5e-3 by default (default variant, ASHRAE 62.1) library default ratOAFlo_P (default variant) ratOAFlo_P (default variant) ratOAFlo_P (default variant) ratOAFlo_P (default variant)
fan_schedule Day schedule of the fans of a balanced (system_d) or extract (system_c) ventilation unit: rows of time since midnight [s] and fraction of the design flow, held until the next row, as "[0, 0.5; 25200, 1; 79200, 0.5]" for half the flow at night; the design flow all day by default library default fanSchedule (system_d, system_c variant) fanSchedule (system_d, system_c variant) fanSchedule (system_d, system_c variant) fanSchedule (system_d, system_c variant)
summer_bypass Whether the balanced ventilation unit (system_d) leads the outdoor air around its heat recovery when the outdoor air is above bypass_outdoor_temperature and cooler than the extract air (free cooling), false by default library default useBypass (system_d variant) useBypass (system_d variant) useBypass (system_d variant) useBypass (system_d variant)
bypass_outdoor_temperature Outdoor temperature above which the summer bypass of the balanced ventilation unit may open [K], 288.15 by default library default TOutByp (system_d variant) TOutByp (system_d variant) TOutByp (system_d variant) TOutByp (system_d variant)
supply_air_minimum_temperature Minimum supply air temperature held by an electric post-heater after the supply fan of the balanced ventilation unit (system_d) [K]; no post-heater when absent library default TSupMin (system_d variant) TSupMin (system_d variant) TSupMin (system_d variant) TSupMin (system_d variant)
post_heater_power Capacity of the electric post-heater of the balanced ventilation unit [W], the design flow heated by 25 K by default library default QHeaPos_flow_nominal (system_d variant) QHeaPos_flow_nominal (system_d variant) QHeaPos_flow_nominal (system_d variant) QHeaPos_flow_nominal (system_d variant)
trickle_vent_dp_nominal Pressure drop of the trickle vents of the rooms at the design flow of the extract ventilation unit (system_c) [Pa], 10 by default library default dpVen_nominal (system_c variant) dpVen_nominal (system_c variant) dpVen_nominal (system_c variant) dpVen_nominal (system_c variant)

BoilerControlParameters

Elements: boilercontrol

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
threshold_outdoor_air_cutoff Outdoor air temperature threshold; output is true when the outdoor air is below this heating cut-off limit [K] 288.15 threshold_outdoor_air_cutoff threshold_outdoor_air_cutoff threshold_outdoor_air_cutoff threshold_outdoor_air_cutoff
threshold_to_switch_off_boiler Tank bottom temperature above which the boiler switches off; defaults to tsup_nominal + 5 K [K] library default threshold_to_switch_off_boiler threshold_to_switch_off_boiler threshold_to_switch_off_boiler threshold_to_switch_off_boiler
tsup_nominal Supply temperature set point; the boiler starts when the tank top drops 1 K below it [K] 353.15 TSup_nominal TSup_nominal TSup_nominal TSup_nominal
temperature_hysteresis Hysteresis of the tank temperature checks that start and stop the boiler (default and complex variants; the simple variant has no such checks); 0 (the default) switches at each threshold crossing, about 1 K avoids their chattering (see the simulation performance page) [K] library default dTHys dTHys dTHys dTHys

BoilerParameters

Elements: boiler

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
coefficients_for_efficiency_curve, efficiency_curve_coefficients Coefficients for efficiency curve {0.9} a a a a
diff_pressure Pressure rise values defining the boiler-circuit pump pressure curve [Pa] 5000*{2,1} dp dp dp dp
dp_nominal Pressure difference [Pa] 5000.0 dp_nominal dp_nominal dp_nominal dp_nominal
dt_boi_nominal Nominal temperature difference for the boiler loop [K] 20.0 - - - -
dt_rad_nominal Nominal temperature difference for the radiator loop [K] 10.0 - - - -
effcur, efficiency_curve Curve used to compute the efficiency Buildings.Fluid.Types.EfficiencyCurves.Constant effCur effCur effCur effCur
fraction_of_nominal_flow_rate_where_flow_transitions_to_laminar, laminar_transition_fraction numerical. Fraction of nominal flow rate where flow transitions to laminar [1] 0.1 deltaM deltaM deltaM deltaM
height_of_tank_without_insulation, tank_height Height of tank (without insulation) [m] 2.0 hTan hTan hTan hTan
if_actual_temperature_at_port_is_computed, show_temperature numerical. = true, if actual temperature at port is computed false show_T show_T show_T show_T
nominal_heating_power Nominal heating power [W] 20000.0 Q_flow_nominal Q_flow_nominal Q_flow_nominal Q_flow_nominal
nominal_mass_flow_radiator_loop Nominal mass flow rate of the radiator loop [kg/s] computed nominal_mass_flow_radiator_loop nominal_mass_flow_radiator_loop nominal_mass_flow_radiator_loop nominal_mass_flow_radiator_loop
nominal_mass_flow_rate_boiler Nominal mass flow rate of the boiler loop [kg/s] computed nominal_mass_flow_rate_boiler nominal_mass_flow_rate_boiler nominal_mass_flow_rate_boiler nominal_mass_flow_rate_boiler
number_of_volume_segments numerical. Number of volume segments [1] 4 nSeg nSeg nSeg nSeg
sca_fac_rad Scaling factor to scale the power (and mass flow rate) of the radiator loop [1] 1.5 - - - -
tank_volume Tank volume [m3] 0.2 VTan VTan VTan VTan
temperature_used_to_compute_nominal_efficiency, nominal_efficiency_temperature Temperature used to compute nominal efficiency (only used if efficiency curve depends on temperature) [K] 353.15 T_nominal T_nominal T_nominal T_nominal
thickness_of_insulation, insulation_thickness Thickness of insulation [m] 0.1 dIns dIns dIns dIns
use_linear_relation_between_m_flow_and_dp_for_any_flow_rate, linearized numerical. = true, use linear relation between m_flow and dp for any flow rate of the boiler (the Modelica default is false) false linearizeFlowResistance linearizeFlowResistance linearizeFlowResistance linearizeFlowResistance
v_flow Volume flow rate values defining the boiler-circuit pump pressure curve [m3/s] computed V_flow V_flow V_flow V_flow
use_storage_tank None false useStorageTank useStorageTank useStorageTank useStorageTank
temperature_heatpump_source, heat_pump_source_temperature Constant source temperature of the heat pump [K], the water loop of the water-water heat pump, or the source of the air-water heat pump when heat_pump_source_outdoor_air is false 286.15 TSouSet TSouSet TSouSet TSouSet
temperature_supply_setpoint_heat_pump, heat_pump_supply_setpoint Supply temperature set point of the heat pump [K]; for the air-water heat pump, the supply temperature of the heating curve at the design outdoor temperature 323.15 TSet TSet TSet TSet
loss_conductance Heat loss conductance of the boiler to its room [W/K], 1e-4 * nominal heating power (0.5 % of it at 50 K) by default; BoilerPolynomial of Buildings 13 subtracts this loss twice from the water library default UA UA UA UA
water_volume Water volume of the boiler [m3], 1.5e-6 * nominal heating power by default library default VWat VWat VWat VWat
dry_mass Dry mass of the boiler lumped to its water [kg], 1.5e-3 * nominal heating power by default library default mDry mDry mDry mDry
insulation_conductivity Thermal conductivity of the tank insulation [W/(m.K)], 0.04 by default library default kIns kIns kIns kIns
ambient_temperature Temperature of the room around the boiler and the tank, for their losses [K], 288.15 by default library default TAmbient TAmbient TAmbient TAmbient
supply_temperature_setpoint Supply temperature set point of the boiler without storage [K], 353.15 by default library default TempSet (without_storage variant) TempSet (without_storage variant) TempSet (without_storage variant) TempSet (without_storage variant)
fuel Fuel of the boiler, a record of Buildings.Fluid.Data.Fuels such as NaturalGasLowerHeatingValue (the default), NaturalGasHigherHeatingValue, HeatingOilLowerHeatingValue or WoodAirDriedLowerHeatingValue library default taken another way taken another way taken another way taken another way
heat_pump_nominal_source_temperature Source temperature at the rating point of the heat pump [K], where it delivers the nominal heating power at the supply temperature set point; the design outdoor temperature (air-water), the coldest ground temperature (ground-source) or the source temperature (water-water) by default library default TEvaHea_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TEvaHea_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TEvaHea_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TEvaHea_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
heat_pump_source_mass_flow Mass flow rate of the source side of the heat pump [kg/s], the one of the performance data scaled to the nominal heating power by default library default mSou_flow_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) mSou_flow_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) mSou_flow_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) mSou_flow_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
heat_pump_source_outdoor_air Whether the evaporator of the air-water heat pump takes the outdoor air of the weather data (true by default) or the constant temperature_heatpump_source (a sweep of the source temperature); Buildings and IDEAS only library default useOutdoorAirSource (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) useOutdoorAirSource (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) useOutdoorAirSource (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) useOutdoorAirSource (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
design_outdoor_temperature Design outdoor temperature of the heating curve of the air-water heat pump [K], 265.15 (-8 degC, Uccle, NBN EN 12831) by default library default TOutDes (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TOutDes (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TOutDes (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TOutDes (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
heating_limit_temperature Outdoor temperature above which the air-water heat pump does not heat [K], 289.15 by default library default TOutHeaLim (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TOutHeaLim (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TOutHeaLim (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TOutHeaLim (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
minimum_supply_temperature Supply temperature of the heating curve of the air-water heat pump at the heating limit [K], 303.15 by default library default TSupMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TSupMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TSupMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TSupMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
buffer_temperature_band Width of the buffer temperature band switching the air-water heat pump on and off around the supply set point [K], 5 by default library default dTHys (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) dTHys (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) dTHys (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) dTHys (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
compressor_minimum_on_time Minimum time the compressor of the air-water heat pump runs once started [s], 300 by default library default minOnTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) minOnTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) minOnTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) minOnTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
compressor_minimum_off_time Minimum time the compressor of the air-water heat pump stays off once stopped [s], 300 by default library default minOffTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) minOffTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) minOffTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) minOffTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
compressor_minimum_speed Lowest speed the compressor of the heat pump runs at, as a fraction of its full speed [1], 0.3 by default. Below the heat this speed delivers the heat pump cannot modulate: it charges its buffer and stops, in cycles (see buffer_temperature_band). At most 0.95, a compressor that hardly modulates: the controller of the speed needs a range between its lowest and its full speed library default yComMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) yComMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) yComMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) yComMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
compressor_controller_gain Gain of the controller holding the supply temperature with the compressor speed [1/K], 0.1 by default: the share of the full speed added per kelvin the condenser outlet is below its set point library default kCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) kCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) kCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) kCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
compressor_controller_integral_time Integral time of the controller of the compressor speed [s], 300 by default library default TiCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TiCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TiCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) TiCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant)
heat_pump_data Performance data of the heat pump (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump): an EN 14511 record of Buildings 13 scaled to the nominal heating power (Vitocal251A08, the default of the air-water heat pump, an 8 kW air-water unit; SingleSplitRXM20R, a 2 kW air-air split; WAMAK_WaterToWater_220kW, a 220 kW water-water unit), table for the tables of heat_pump_table_heating_capacity and heat_pump_table_electrical_power, or carnot (the default of the ground-source and water-water heat pumps) for a constant Carnot effectiveness heat_pump_carnot_effectiveness library default - - - -
heat_pump_carnot_effectiveness Carnot effectiveness of the heat pump when heat_pump_data is carnot [1]: the COP is this fraction of the Carnot COP between the condenser outlet plus 5 K and the source minus 5 K (air) or 2 K (water); 0.45 by default, about 3.7 at A7/W35 and 4.4 at B0/W35 library default - - - -
heat_pump_table_source_temperatures Source temperatures of the performance tables of the heat pump (heat_pump_data table) [K], the columns of the tables, increasing library default - - - -
heat_pump_table_condenser_temperatures Condenser outlet (supply) temperatures of the performance tables of the heat pump (heat_pump_data table) [K], the rows of the tables, increasing library default - - - -
heat_pump_table_heating_capacity Heating capacity table of the heat pump (heat_pump_data table) [W]: one row per condenser temperature, the values per source temperature separated by commas, the rows by semicolons, as "4490, 5170, 6470; 4230, 4900, 6260"; a 0 marks a point outside the operating envelope library default - - - -
heat_pump_table_electrical_power Electrical power table of the heat pump (heat_pump_data table) [W], laid out as heat_pump_table_heating_capacity library default - - - -
ground_temperature_mean Mean temperature of the ground loop of the ground-source heat pump over the year [K], 283.15 by default library default TGroMea (ground_source_heat_pump variant) TGroMea (ground_source_heat_pump variant) TGroMea (ground_source_heat_pump variant) TGroMea (ground_source_heat_pump variant)
ground_temperature_amplitude Amplitude of the annual variation of the ground loop temperature of the ground-source heat pump [K], 3 by default (the loop is coldest at the end of the heating season) library default TGroAmp (ground_source_heat_pump variant) TGroAmp (ground_source_heat_pump variant) TGroAmp (ground_source_heat_pump variant) TGroAmp (ground_source_heat_pump variant)
ground_coldest_day Day of the year when the ground loop of the ground-source heat pump is coldest [d], 45 (mid-February) by default library default groColDay (ground_source_heat_pump variant) groColDay (ground_source_heat_pump variant) groColDay (ground_source_heat_pump variant) groColDay (ground_source_heat_pump variant)
temperature_initial Initial temperature of the boiler and of the tank water [K], 293.15 by default library default T_start T_start T_start T_start

DuctParameters

Elements: duct

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
nominal_mass_flow_rate Nominal air mass flow rate through the duct [kg/s] 100*1.2/3600 m_flow_nominal m_flow_nominal m_flow_nominal m_flow_nominal
dp_nominal Pressure drop of the duct at the nominal flow [Pa] 40.0 dp_nominal dp_nominal dp_nominal dp_nominal

EmissionControlParameters

Elements: emissioncontrol

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
schedule Schedule of switching times that toggles the heating set point between the occupied set point and the setback value 3600*{7, 19} schedule schedule schedule schedule
temperature_heating_setpoint Room air temperature heating set point during occupied period [K], 21 degC by default (the design indoor temperature of dwellings) 294.15 THeaSet THeaSet THeaSet THeaSet
temperature_heating_setback Room air temperature heating set point during the setback period (e.g. at night) [K] 289.0 THeaSetBack THeaSetBack THeaSetBack THeaSetBack
controller_gain Gain of controller [1] 5.0 k k k k
heating_loop_gain Gain of the heating loop of the default (PI) control of an emitter [1/K], 0.1 by default: the opening added per kelvin the room is below its set point library default kHeaCon (default variant) kHeaCon (default variant) kHeaCon (default variant) kHeaCon (default variant)
heating_loop_integral_time Integral time of the heating loop of the default (PI) control of an emitter [s], 900 by default library default TiHeaCon (default variant) TiHeaCon (default variant) TiHeaCon (default variant) TiHeaCon (default variant)
on_off_band Band of the on/off control of an emitter (variant onoff) [K], 0.1 by default: the emitter opens when the room is half the band below its set point and closes when it is half the band above library default bandwidth (onoff variant) bandwidth (onoff variant) bandwidth (onoff variant) bandwidth (onoff variant)
data Occupancy data sources library default data data data data

IdealHeatingCoolingParameter

Elements: idealheatingcooling

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
controller_gain Gain of the heating and cooling PI controllers, output fraction of the capacity per kelvin of error [1/K] 0.1 k k k k
controller_integral_time Integral time of the heating and cooling PI controllers [s] 300.0 Ti Ti Ti Ti
cooling_setpoint_schedule Day schedule of the cooling set point, rows of time since midnight [s] and set point [K], repeated every day; linear between rows, repeat a time for a step; one row for a constant set point [0, 300.15] TSetCoo TSetCoo TSetCoo TSetCoo
heating_setpoint_schedule Day schedule of the heating set point, rows of time since midnight [s] and set point [K], repeated every day; linear between rows, repeat a time for a step; one row for a constant set point [0, 293.15] TSetHea TSetHea TSetHea TSetHea
maximum_cooling_power Cooling capacity; zero switches cooling off [W] 1000000.0 QCoo_flow_max QCoo_flow_max QCoo_flow_max QCoo_flow_max
maximum_heating_power Heating capacity; zero switches heating off [W] 1000000.0 QHea_flow_max QHea_flow_max QHea_flow_max QHea_flow_max
radiative_fraction Fraction of the heat flow exchanged with the radiative temperature of the zone, the rest with its air [1] 0.0 frad frad frad frad

OccupancyParameters

Elements: occupancy

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
gain Gain to convert from occupancy (per person) to radiant, convective and latent heat in [W/m2] [35; 70; 30] gain gain gain gain
heat_gain_if_occupied, occupant_density Heat gain if occupied 1/6/4 k k k k
occupancy Occupancy table, each entry switching occupancy on or off 3600*{7, 19} occupancy occupancy occupancy occupancy
ach deprecated: the infiltration of a zone is the ach parameter of its space. Infiltration [1/h] 0.9 ACH ACH ACH ACH
floor_area Floor area [m2] library default AFlo (co2 variant) AFlo (co2 variant) - -
data Occupancy data sources library default data data data data
sensible_heat_per_person Sensible heat released per occupant [W]; with the latent heat and the radiant fraction it gives the gain matrix when that one is absent library default taken another way taken another way taken another way taken another way
latent_heat_per_person Latent heat released per occupant [W] library default taken another way taken another way taken another way taken another way
radiant_fraction Radiant share of the sensible heat of the occupants [1] library default taken another way taken another way taken another way taken another way
lighting_power_density Heat released by the lighting per floor area, all day [W/m2] library default lightingPower - taken another way lightingPower
lighting_radiant_fraction Radiant share of the lighting heat [1], 0.4 by default library default lightingRadiantFraction - taken another way lightingRadiantFraction
equipment_power_density Heat released by the equipment per floor area, all day [W/m2] library default equipmentPower - taken another way equipmentPower
equipment_radiant_fraction Radiant share of the equipment heat [1], 0.4 by default library default equipmentRadiantFraction - taken another way equipmentRadiantFraction
activity_degree Activity level of the occupants of the reduced-order zone [met], 1.2 by default library default - - taken another way -
co2_generation_per_person CO2 released per occupant [m3/s], 5.2e-6 by default (CO2 variant) library default gCO2 (co2 variant) gCO2 (co2 variant) - -
outdoor_co2_concentration CO2 concentration of the outdoor air [ppm], 420 by default (CO2 variant) library default ppmOut (co2 variant) ppmOut (co2 variant) - -

PIDParameters

Elements: collectorcontrol

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
controller_type Type of controller Buildings.Controls.OBC.CDL.Types.SimpleController.P controllerType controllerType controllerType controllerType
k Gain of controller [1] 1.0 k k k k
nd The higher Nd, the more ideal the derivative block [1] 10.0 Nd Nd Nd Nd
ni Ni*Ti is time constant of anti-windup compensation [1] 0.9 Ni Ni Ni Ni
r Typical range of control error, used for scaling the control error 1.0 r r r r
td Time constant of derivative block [s] 0.1 Td Td Td Td
ti Time constant of integrator block [s] 0.5 Ti Ti Ti Ti
y_max Upper limit of output [1] 1.0 yMax yMax yMax yMax
y_min Lower limit of output [1] 0.0 yMin yMin yMin yMin

PhotovoltaicParameters

Elements: photovoltaic

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
area Module area [m2] 20.0 A A A A
efficiency Module and inverter efficiency [1] 0.18 eta eta eta eta
azimuth Surface azimuth [deg], 0 for south, 90 for west 0.0 - - - -
tilt Surface tilt [deg], 0 for a roof, 90 for a wall 35.0 - - - -
active_area_fraction Share of the module area covered by active cells [1], 0.9 by default library default fAct fAct fAct fAct
inverter_efficiency Efficiency of the DC to AC conversion [1], 0.9 by default library default eta_DCAC eta_DCAC eta_DCAC eta_DCAC
power_factor Power factor of the inverter [1], 0.9 by default library default pf pf pf pf
tilt_radians Surface tilt [rad], from the tilt in degrees computed til til til til
azimuth_radians Surface azimuth [rad], from the azimuth in degrees computed azi azi azi azi

PumpParameters

Elements: pump

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
constant_input_set_point deprecated: it never reached the pump model and has no effect. Constant input set point library default - - - -
dp_nominal Nominal pressure raise [Pa] 30000.0 dp_nominal dp_nominal dp_nominal dp_nominal
m_flow_nominal Nominal mass flow rate [kg/s] 0.15 m_flow_nominal m_flow_nominal m_flow_nominal m_flow_nominal

RadiatorParameter

Elements: radiator

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
air_temperature_at_nominal_condition, air_temperature Air temperature at nominal condition [K] 293.15 TAir_nominal TAir_nominal TAir_nominal TAir_nominal
dp_nominal Pressure drop at nominal mass flow rate [Pa] 2000.0 dp_nominal dp_nominal dp_nominal dp_nominal
dry_mass_of_radiator_that_will_be_lumped_to_water_heat_capacity, dry_mass Dry mass of radiator that will be lumped to water heat capacity [kg] computed mDry mDry mDry mDry
exponent_for_heat_transfer, heat_transfer_exponent Exponent for heat transfer 1.24 n n n n
fraction_of_nominal_mass_flow_rate_where_transition_to_turbulent_occurs, turbulent_transition_fraction numerical. Fraction of nominal mass flow rate where transition to turbulent occurs [1] 0.01 deltaM deltaM deltaM deltaM
fraction_radiant_heat_transfer, radiant_fraction Fraction radiant heat transfer [1] 0.3 fraRad fraRad fraRad fraRad
nominal_heating_power_positive_for_heating, nominal_heating_power Nominal heating power (positive for heating) [W] 5000.0 Q_flow_nominal Q_flow_nominal Q_flow_nominal Q_flow_nominal
number_of_elements_used_in_the_discretization, number_of_elements numerical. Number of elements used in the discretization [1] 1 nEle nEle nEle nEle
radiative_temperature_at_nominal_condition, radiative_temperature Radiative temperature at nominal condition [K] 293.15 TRad_nominal TRad_nominal TRad_nominal TRad_nominal
use_linear_relation_between_m_flow_and_dp_for_any_flow_rate, linearized numerical. = true, use linear relation between m_flow and dp for any flow rate true linearized linearized linearized linearized
use_m_flow_f_dp_else_dp_f_m_flow, from_dp numerical. = true, use m_flow = f(dp) else dp = f(m_flow) false from_dp from_dp from_dp from_dp
water_inlet_temperature_at_nominal_condition, water_inlet_temperature Water inlet temperature at nominal condition [K] 353.15 T_a_nominal T_a_nominal T_a_nominal T_a_nominal
water_outlet_temperature_at_nominal_condition, water_outlet_temperature Water outlet temperature at nominal condition [K] 333.15 T_b_nominal T_b_nominal T_b_nominal T_b_nominal
water_volume_of_radiator, water_volume Water volume of radiator [m3] computed VWat VWat VWat VWat

SensorParameters

Elements: temperaturesensor, heatmetersensor

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
nominal_mass_flow_rate Nominal mass flow rate through the sensor, used for its dynamics and its small-flow regularization [kg/s] 0.15 m_flow_nominal m_flow_nominal m_flow_nominal m_flow_nominal
time_constant Time constant of the sensor [s], 1 by default; 0 for an ideal sensor library default tau tau tau tau

SpaceParameter

Elements: space

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
average_room_height Average room height [m] 2.0 hRoo hZone - -
floor_area Floor area [m2] 20.0 AFlo taken another way AZone AFlo
linearize_emissive_power numerical. Set to true to linearize emissive power true linearizeRadiation - - -
nominal_mass_flow_rate Nominal mass flow rate [kg/s] 0.01 m_flow_nominal m_flow_nominal (when given) - -
sensible_thermal_mass_scaling_factor Factor for scaling the sensible thermal mass of the zone air volume [1] 1.0 mSenFac mSenFac mSenFac (when given) -
ach Infiltration [1/h] library default ACH (infiltration variant) taken another way taken another way taken another way
ventilation_schedule Day schedule of outdoor air brought into the zone on top of the infiltration, rows of time since midnight [s] and mass flow rate [kg/s], repeated every day (Buildings infiltration variant) library default ventilationSchedule (infiltration variant) taken another way - -
temperature_initial Initial temperature [K] 294.15 T_start T_start T_start (when given) -
volume Air volume of the zone [m3] computed - V VAir VRoo
n50 Air change rate at a 50 Pa pressure difference, the airtightness of the zone [1/h]; gives the infiltration ach as n50 / n50_to_ach when ach is absent (IDEAS takes it directly) library default taken another way taken another way taken another way taken another way
n50_to_ach Ratio between the air change rate at 50 Pa and the infiltration rate [1] 20.0 taken another way n50toAch (when given) taken another way taken another way
interior_convection_coefficient Fixed convective heat transfer coefficient of the inside surfaces [W/(m2.K)]; Buildings and the ISO 13790 zone switch to a fixed coefficient (3 and 3.45 by default), the reduced-order zone applies it to its walls, windows, floor and roof (2.7 by default) library default hIntFixed - taken another way hInt
exterior_convection_coefficient Fixed convective heat transfer coefficient of the outside surfaces [W/(m2.K)]; Buildings switches to a fixed coefficient (10 by default), the reduced-order zone applies it to its walls, windows and roof (20 by default) library default hExtFixed - taken another way -
thermal_mass_class Building mass class of the ISO 13790 zone, light, medium or heavy; derived from the heat capacity of the constructions when absent library default - - - taken another way
ground_heat_transfer_factor Adjustment factor of the heat transfer through the floor to the ground of the ISO 13790 zone [1], 0.5 by default library default - - - b
shading_reduction_factor Factor on the solar gains through the windows for external shading [1]; the ISO 13790 zone applies it always (1 by default), the reduced-order zone when the irradiance exceeds the sunblind threshold (0.7 by default) library default - - taken another way shaRedFac
sunblind_irradiance_threshold Irradiance on a window above which the reduced-order zone applies the shading reduction factor [W/m2], 100 by default library default - - taken another way -

SplitValveParameters

Elements: splitvalve

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
dp_nominal Pressure drop at nominal mass flow rate, set to zero or negative number at outflowing ports [Pa] {5000,-1,-1} dp_nominal dp_nominal dp_nominal dp_nominal
fraction_of_nominal_mass_flow_rate_where_transition_to_turbulent_occurs, turbulent_transition_fraction numerical. Fraction of nominal mass flow rate where transition to turbulent occurs [1] 0.3 deltaM deltaM deltaM deltaM
m_flow_nominal Mass flow rate; set negative at outflowing ports [kg/s] 0.15*{1,-1,-1} m_flow_nominal m_flow_nominal m_flow_nominal m_flow_nominal
nominal_mass_flow_rate_for_dynamic_momentum_and_energy_balance, dynamic_nominal_mass_flow_rate numerical. Nominal mass flow rate for dynamic momentum and energy balance [kg/s] library default mDyn_flow_nominal mDyn_flow_nominal mDyn_flow_nominal mDyn_flow_nominal
time_constant_at_nominal_flow_for_dynamic_energy_and_momentum_balance, time_constant numerical. Time constant at nominal flow for dynamic energy and momentum balance [s] library default tau tau tau tau
use_linear_relation_between_m_flow_and_dp_for_any_flow_rate, linearized numerical. = true, use linear relation between m_flow and dp for any flow rate true linearized linearized linearized linearized

ThreeWayValveControlParameters

Elements: threewayvalvecontrol

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
controller_type Type of controller Buildings.Controls.OBC.CDL.Types.SimpleController.P controllerType controllerType controllerType controllerType
k Gain of controller [1] 1.0 k k k k
nd The higher Nd, the more ideal the derivative block [1] 10.0 Nd Nd Nd Nd
ni Ni*Ti is time constant of anti-windup compensation [1] 0.9 Ni Ni Ni Ni
r Typical range of control error, used for scaling the control error 1.0 r r r r
td Time constant of derivative block [s] 0.1 Td Td Td Td
ti Time constant of integrator block [s] 0.5 Ti Ti Ti Ti
y_max Upper limit of output [1] 1.0 yMax yMax yMax yMax
y_min Lower limit of output [1] 0.0 yMin yMin yMin yMin
supply_temperature_setpoint Temperature the valve holds after it, at its temperature sensor [K]. Only a valve with its pump downstream (mixing circuit) can lower the supply temperature; with the pump upstream it can only cut the flow. 363.15 (90 degC) by default, raised 5 K above the highest supply of a storage boiler feeding a valve with its pump upstream (the top of the tank, 15 K above the boiler set point) so that the valve does not close. library default - - - -

ThreeWayValveParameters

Elements: threewayvalve

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
Av Av (metric) flow coefficient [m2] library default Av Av Av Av
Cv Cv (US) flow coefficient [USG/min/(psi)^(1/2)] library default Cv Cv Cv Cv
Kv Kv (metric) flow coefficient [m3/h/(bar)^(1/2)] library default Kv Kv Kv Kv
dp_fixed_nominal Nominal pressure drop of pipes and other equipment in flow legs at port_1 and port_3 [Pa] {2000,0} dpFixed_nominal dpFixed_nominal dpFixed_nominal dpFixed_nominal
dp_valve_nominal Nominal pressure drop of fully open valve, used if CvData=Buildings.Fluid.Types.CvTypes.OpPoint [Pa] 6000.0 dpValve_nominal dpValve_nominal dpValve_nominal dpValve_nominal
fra_k Fraction Kv(port_3->port_2)/Kv(port_1->port_2) [1] 0.7 fraK fraK fraK fraK
fraction_of_nominal_flow_rate_where_linearization_starts_if_y_1, linearization_start_fraction numerical. Fraction of nominal flow rate where linearization starts, if y=1 [1] 0.02 deltaM deltaM deltaM deltaM
m_flow_nominal Nominal mass flow rate [kg/s] 0.15 m_flow_nominal m_flow_nominal m_flow_nominal m_flow_nominal
range_of_significant_deviation_from_equal_percentage_law, equal_percentage_deviation Range of significant deviation from equal percentage law [1] 0.01 delta0 delta0 delta0 delta0
rangeability Rangeability, R=50...100 typically [1] 50.0 R R R R
rho_std, standard_density Inlet density for which valve coefficients are defined [kg/m3] library default rhoStd rhoStd rhoStd rhoStd
use_linear_relation_between_m_flow_and_dp_for_any_flow_rate, linearized numerical. = true, use linear relation between m_flow and dp for any flow rate {true, true} linearized linearized linearized linearized
valve_leakage Valve leakage, l=Kv(y=0)/Kv(y=1) [1] {0.01,0.01} l l l l
flow_coefficient_type How the flow coefficients of the valve are given, OpPoint (the nominal pressure drop, the library default), Kv, Cv or Av; without it Kv, Cv and Av are ignored library default taken another way taken another way taken another way taken another way
actuator_stroke_time Time the actuator takes to open or close the valve [s], 120 by default library default strokeTime riseTime strokeTime strokeTime

ValveParameters

Elements: valve

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
av Av (metric) flow coefficient [m2] library default Av Av Av Av
cv Cv (US) flow coefficient [USG/min/(psi)^(1/2)] library default Cv Cv Cv Cv
dp_fixed_nominal Pressure drop of pipe and other resistances that are in series [Pa] 5000.0 dpFixed_nominal dpFixed_nominal dpFixed_nominal dpFixed_nominal
dp_valve_nominal Nominal pressure drop of fully open valve, used if CvData=Buildings.Fluid.Types.CvTypes.OpPoint [Pa] 10000.0 dpValve_nominal dpValve_nominal dpValve_nominal dpValve_nominal
fraction_of_nominal_flow_rate_where_linearization_starts_if_y_1, linearization_start_fraction numerical. Fraction of nominal flow rate where linearization starts, if y=1 [1] 0.02 deltaM deltaM deltaM deltaM
k_fixed Flow coefficient of fixed resistance that may be in series with valve, k=m_flow/sqrt(dp), with unit=(kg.m)^(1/2) library default kFixed kFixed kFixed kFixed
kv Kv (metric) flow coefficient [m3/h/(bar)^(1/2)] library default Kv Kv Kv Kv
m_flow_nominal Nominal mass flow rate [kg/s] 0.06 m_flow_nominal m_flow_nominal m_flow_nominal m_flow_nominal
range_of_significant_deviation_from_equal_percentage_law, equal_percentage_deviation Range of significant deviation from equal percentage law [1] 0.01 delta0 delta0 delta0 delta0
rangeability Rangeability, R=50...100 typically [1] 50.0 R R R R
use_linear_relation_between_m_flow_and_dp_for_any_flow_rate, linearized numerical. = true, use linear relation between m_flow and dp for any flow rate true linearized linearized linearized linearized
use_m_flow_f_dp_else_dp_f_m_flow, from_dp numerical. = true, use m_flow = f(dp) else dp = f(m_flow) true from_dp from_dp from_dp from_dp
valve_leakage Valve leakage, l=Kv(y=0)/Kv(y=1) [1] 0.0001 l l l l
flow_coefficient_type How the flow coefficient of the valve is given, OpPoint (the nominal pressure drop, the library default), Kv, Cv or Av; without it kv, cv and av are ignored library default taken another way taken another way taken another way taken another way
standard_density Inlet density for which the flow coefficients are defined [kg/m3], water at 4 degC by default library default rhoStd rhoStd rhoStd rhoStd
actuator_stroke_time Time the actuator takes to open or close the valve [s], 120 by default library default strokeTime riseTime strokeTime strokeTime

VavParameters

Elements: vav

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
nominal_mass_flow_rate Nominal air mass flow rate of the damper [kg/s] 100*1.2/3600 m_flow_nominal (default variant) m_flow_nominal (default variant) m_flow_nominal (default variant) m_flow_nominal (default variant)
damper_dp_nominal Pressure drop of the fully open damper at the nominal flow [Pa] 50.0 dpDamper_nominal (default variant) dpDamper_nominal (default variant) dpDamper_nominal (default variant) dpDamper_nominal (default variant)
fixed_dp_nominal Pressure drop of the duct and the other resistances in series with the damper at the nominal flow [Pa] 50.0 dpFixed_nominal (default variant) dpFixed_nominal (default variant) dpFixed_nominal (default variant) dpFixed_nominal (default variant)
cooling_air_flow_nominal Design air mass flow rate for cooling of the VAV box [kg/s] (complex variant) 100*1.2/3600 mCooAir_flow_nominal (complex variant) mCooAir_flow_nominal (complex variant) mCooAir_flow_nominal (complex variant) mCooAir_flow_nominal (complex variant)
heating_air_flow_nominal Design air mass flow rate for heating of the VAV box [kg/s] (complex variant) 100*1.2/3600 mHeaAir_flow_nominal (complex variant) mHeaAir_flow_nominal (complex variant) mHeaAir_flow_nominal (complex variant) mHeaAir_flow_nominal (complex variant)
room_volume Volume of the room the VAV box serves [m3] (complex variant) 100.0 VRoo (complex variant) VRoo (complex variant) VRoo (complex variant) VRoo (complex variant)
heating_water_inlet_temperature Reheat water inlet temperature at the design point [K] (complex variant) 363.15 THeaWatInl_nominal (complex variant) THeaWatInl_nominal (complex variant) THeaWatInl_nominal (complex variant) THeaWatInl_nominal (complex variant)
heating_water_outlet_temperature Reheat water outlet temperature at the design point [K] (complex variant) 333.15 THeaWatOut_nominal (complex variant) THeaWatOut_nominal (complex variant) THeaWatOut_nominal (complex variant) THeaWatOut_nominal (complex variant)
heating_air_inlet_temperature Air inlet temperature of the box at the heating design point [K] (complex variant) 303.15 THeaAirInl_nominal (complex variant) THeaAirInl_nominal (complex variant) THeaAirInl_nominal (complex variant) THeaAirInl_nominal (complex variant)
heating_air_discharge_temperature Discharge air temperature of the box at the heating design point [K] (complex variant) 298.15 THeaAirDis_nominal (complex variant) THeaAirDis_nominal (complex variant) THeaAirDis_nominal (complex variant) THeaAirDis_nominal (complex variant)

WeatherParameters

Elements: weather

Parameter Description Default Buildings IDEAS AixLib reduced order ISO 13790
path Name of weather data file library default filNam filNam filNam filNam
atmospheric_pressure_source Source of the atmospheric pressure, e.g. Buildings.BoundaryConditions.Types.DataSource.File to read it from the weather file; the library default (a constant 101325 Pa) when absent library default pAtmSou - pAtmSou pAtmSou
atmospheric_pressure Atmospheric pressure [Pa] when it is not read from the weather file, 101325 by default library default pAtm - pAtm pAtm
outdoor_co2_concentration CO2 concentration of the outdoor air of the IDEAS simulation manager [ppm], 400 by default library default - ppmCO2 - -
building_height Height of the building [m] for the wind speed profile of the IDEAS simulation manager, 10 by default library default - H - -
default_n50 Air change rate at 50 Pa of the IDEAS zones that do not give their own [1/h], 3 by default library default - n50 - -