Parameters
Every parameter is optional: a parameter left out of the YAML is not written to the Modelica model, so the library's own default applies ("library default" below), unless trano has a default of its own. The library columns give the Modelica name the parameter is rendered under; a dash means the library does not take it (a value given anyway is ignored with a warning). numerical marks simulation settings rather than physical properties. The page is generated from trano/data_models/parameters.yaml.
AhuParameters
Elements: airhandlingunit
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
m_flow_nominal |
Nominal mass flow rate [kg/s] | 2*100*1.2/3600 |
mAir_flow_nominal (when given; default variant); m_flow_nominal (test, system_d, system_c variant) |
mAir_flow_nominal (when given; default variant); m_flow_nominal (test, system_d, system_c variant) |
mAir_flow_nominal (when given; default variant); m_flow_nominal (test, system_d, system_c variant) |
mAir_flow_nominal (when given; default variant); m_flow_nominal (test, system_d, system_c variant) |
dp_nominal |
Nominal pressure raise [Pa] | 200 |
dp_nominal (test, system_d, system_c variant) |
dp_nominal (test, system_d, system_c variant) |
dp_nominal (test, system_d, system_c variant) |
dp_nominal (test, system_d, system_c variant) |
heat_exchanger_effectiveness |
Heat exchanger effectiveness [1] | 0.8 |
eps (test, system_d variant) |
eps (test, system_d variant) |
eps (test, system_d variant) |
eps (test, system_d variant) |
supply_dp_nominal |
Pressure rise of the supply fan [Pa], the nominal pressure rise by default | library default | dpSup_nominal (test, system_d variant) |
dpSup_nominal (test, system_d variant) |
dpSup_nominal (test, system_d variant) |
dpSup_nominal (test, system_d variant) |
return_dp_nominal |
Pressure rise of the return fan [Pa], the nominal pressure rise by default | library default | dpRet_nominal (test, system_d variant) |
dpRet_nominal (test, system_d variant) |
dpRet_nominal (test, system_d variant) |
dpRet_nominal (test, system_d variant) |
building_static_pressure |
Static pressure of the building the supply fan maintains [Pa], 12 by default (default variant) | library default | dpBuiStaSet (default variant) |
dpBuiStaSet (default variant) |
dpBuiStaSet (default variant) |
dpBuiStaSet (default variant) |
outdoor_air_per_area |
Outdoor air flow per floor area [m3/(s.m2)], 0.3e-3 by default (default variant, ASHRAE 62.1) | library default | ratOAFlo_A (default variant) |
ratOAFlo_A (default variant) |
ratOAFlo_A (default variant) |
ratOAFlo_A (default variant) |
outdoor_air_per_person |
Outdoor air flow per person [m3/s], 2.5e-3 by default (default variant, ASHRAE 62.1) | library default | ratOAFlo_P (default variant) |
ratOAFlo_P (default variant) |
ratOAFlo_P (default variant) |
ratOAFlo_P (default variant) |
fan_schedule |
Day schedule of the fans of a balanced (system_d) or extract (system_c) ventilation unit: rows of time since midnight [s] and fraction of the design flow, held until the next row, as "[0, 0.5; 25200, 1; 79200, 0.5]" for half the flow at night; the design flow all day by default | library default | fanSchedule (system_d, system_c variant) |
fanSchedule (system_d, system_c variant) |
fanSchedule (system_d, system_c variant) |
fanSchedule (system_d, system_c variant) |
summer_bypass |
Whether the balanced ventilation unit (system_d) leads the outdoor air around its heat recovery when the outdoor air is above bypass_outdoor_temperature and cooler than the extract air (free cooling), false by default | library default | useBypass (system_d variant) |
useBypass (system_d variant) |
useBypass (system_d variant) |
useBypass (system_d variant) |
bypass_outdoor_temperature |
Outdoor temperature above which the summer bypass of the balanced ventilation unit may open [K], 288.15 by default | library default | TOutByp (system_d variant) |
TOutByp (system_d variant) |
TOutByp (system_d variant) |
TOutByp (system_d variant) |
supply_air_minimum_temperature |
Minimum supply air temperature held by an electric post-heater after the supply fan of the balanced ventilation unit (system_d) [K]; no post-heater when absent | library default | TSupMin (system_d variant) |
TSupMin (system_d variant) |
TSupMin (system_d variant) |
TSupMin (system_d variant) |
post_heater_power |
Capacity of the electric post-heater of the balanced ventilation unit [W], the design flow heated by 25 K by default | library default | QHeaPos_flow_nominal (system_d variant) |
QHeaPos_flow_nominal (system_d variant) |
QHeaPos_flow_nominal (system_d variant) |
QHeaPos_flow_nominal (system_d variant) |
trickle_vent_dp_nominal |
Pressure drop of the trickle vents of the rooms at the design flow of the extract ventilation unit (system_c) [Pa], 10 by default | library default | dpVen_nominal (system_c variant) |
dpVen_nominal (system_c variant) |
dpVen_nominal (system_c variant) |
dpVen_nominal (system_c variant) |
BoilerControlParameters
Elements: boilercontrol
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
threshold_outdoor_air_cutoff |
Outdoor air temperature threshold; output is true when the outdoor air is below this heating cut-off limit [K] | 288.15 |
threshold_outdoor_air_cutoff |
threshold_outdoor_air_cutoff |
threshold_outdoor_air_cutoff |
threshold_outdoor_air_cutoff |
threshold_to_switch_off_boiler |
Tank bottom temperature above which the boiler switches off; defaults to tsup_nominal + 5 K [K] | library default | threshold_to_switch_off_boiler |
threshold_to_switch_off_boiler |
threshold_to_switch_off_boiler |
threshold_to_switch_off_boiler |
tsup_nominal |
Supply temperature set point; the boiler starts when the tank top drops 1 K below it [K] | 353.15 |
TSup_nominal |
TSup_nominal |
TSup_nominal |
TSup_nominal |
temperature_hysteresis |
Hysteresis of the tank temperature checks that start and stop the boiler (default and complex variants; the simple variant has no such checks); 0 (the default) switches at each threshold crossing, about 1 K avoids their chattering (see the simulation performance page) [K] | library default | dTHys |
dTHys |
dTHys |
dTHys |
BoilerParameters
Elements: boiler
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
coefficients_for_efficiency_curve, efficiency_curve_coefficients |
Coefficients for efficiency curve | {0.9} |
a |
a |
a |
a |
diff_pressure |
Pressure rise values defining the boiler-circuit pump pressure curve [Pa] | 5000*{2,1} |
dp |
dp |
dp |
dp |
dp_nominal |
Pressure difference [Pa] | 5000.0 |
dp_nominal |
dp_nominal |
dp_nominal |
dp_nominal |
dt_boi_nominal |
Nominal temperature difference for the boiler loop [K] | 20.0 |
- | - | - | - |
dt_rad_nominal |
Nominal temperature difference for the radiator loop [K] | 10.0 |
- | - | - | - |
effcur, efficiency_curve |
Curve used to compute the efficiency | Buildings.Fluid.Types.EfficiencyCurves.Constant |
effCur |
effCur |
effCur |
effCur |
fraction_of_nominal_flow_rate_where_flow_transitions_to_laminar, laminar_transition_fraction |
numerical. Fraction of nominal flow rate where flow transitions to laminar [1] | 0.1 |
deltaM |
deltaM |
deltaM |
deltaM |
height_of_tank_without_insulation, tank_height |
Height of tank (without insulation) [m] | 2.0 |
hTan |
hTan |
hTan |
hTan |
if_actual_temperature_at_port_is_computed, show_temperature |
numerical. = true, if actual temperature at port is computed | false |
show_T |
show_T |
show_T |
show_T |
nominal_heating_power |
Nominal heating power [W] | 20000.0 |
Q_flow_nominal |
Q_flow_nominal |
Q_flow_nominal |
Q_flow_nominal |
nominal_mass_flow_radiator_loop |
Nominal mass flow rate of the radiator loop [kg/s] | computed | nominal_mass_flow_radiator_loop |
nominal_mass_flow_radiator_loop |
nominal_mass_flow_radiator_loop |
nominal_mass_flow_radiator_loop |
nominal_mass_flow_rate_boiler |
Nominal mass flow rate of the boiler loop [kg/s] | computed | nominal_mass_flow_rate_boiler |
nominal_mass_flow_rate_boiler |
nominal_mass_flow_rate_boiler |
nominal_mass_flow_rate_boiler |
number_of_volume_segments |
numerical. Number of volume segments [1] | 4 |
nSeg |
nSeg |
nSeg |
nSeg |
sca_fac_rad |
Scaling factor to scale the power (and mass flow rate) of the radiator loop [1] | 1.5 |
- | - | - | - |
tank_volume |
Tank volume [m3] | 0.2 |
VTan |
VTan |
VTan |
VTan |
temperature_used_to_compute_nominal_efficiency, nominal_efficiency_temperature |
Temperature used to compute nominal efficiency (only used if efficiency curve depends on temperature) [K] | 353.15 |
T_nominal |
T_nominal |
T_nominal |
T_nominal |
thickness_of_insulation, insulation_thickness |
Thickness of insulation [m] | 0.1 |
dIns |
dIns |
dIns |
dIns |
use_linear_relation_between_m_flow_and_dp_for_any_flow_rate, linearized |
numerical. = true, use linear relation between m_flow and dp for any flow rate of the boiler (the Modelica default is false) | false |
linearizeFlowResistance |
linearizeFlowResistance |
linearizeFlowResistance |
linearizeFlowResistance |
v_flow |
Volume flow rate values defining the boiler-circuit pump pressure curve [m3/s] | computed | V_flow |
V_flow |
V_flow |
V_flow |
use_storage_tank |
None | false |
useStorageTank |
useStorageTank |
useStorageTank |
useStorageTank |
temperature_heatpump_source, heat_pump_source_temperature |
Constant source temperature of the heat pump [K], the water loop of the water-water heat pump, or the source of the air-water heat pump when heat_pump_source_outdoor_air is false | 286.15 |
TSouSet |
TSouSet |
TSouSet |
TSouSet |
temperature_supply_setpoint_heat_pump, heat_pump_supply_setpoint |
Supply temperature set point of the heat pump [K]; for the air-water heat pump, the supply temperature of the heating curve at the design outdoor temperature | 323.15 |
TSet |
TSet |
TSet |
TSet |
loss_conductance |
Heat loss conductance of the boiler to its room [W/K], 1e-4 * nominal heating power (0.5 % of it at 50 K) by default; BoilerPolynomial of Buildings 13 subtracts this loss twice from the water | library default | UA |
UA |
UA |
UA |
water_volume |
Water volume of the boiler [m3], 1.5e-6 * nominal heating power by default | library default | VWat |
VWat |
VWat |
VWat |
dry_mass |
Dry mass of the boiler lumped to its water [kg], 1.5e-3 * nominal heating power by default | library default | mDry |
mDry |
mDry |
mDry |
insulation_conductivity |
Thermal conductivity of the tank insulation [W/(m.K)], 0.04 by default | library default | kIns |
kIns |
kIns |
kIns |
ambient_temperature |
Temperature of the room around the boiler and the tank, for their losses [K], 288.15 by default | library default | TAmbient |
TAmbient |
TAmbient |
TAmbient |
supply_temperature_setpoint |
Supply temperature set point of the boiler without storage [K], 353.15 by default | library default | TempSet (without_storage variant) |
TempSet (without_storage variant) |
TempSet (without_storage variant) |
TempSet (without_storage variant) |
fuel |
Fuel of the boiler, a record of Buildings.Fluid.Data.Fuels such as NaturalGasLowerHeatingValue (the default), NaturalGasHigherHeatingValue, HeatingOilLowerHeatingValue or WoodAirDriedLowerHeatingValue | library default | taken another way | taken another way | taken another way | taken another way |
heat_pump_nominal_source_temperature |
Source temperature at the rating point of the heat pump [K], where it delivers the nominal heating power at the supply temperature set point; the design outdoor temperature (air-water), the coldest ground temperature (ground-source) or the source temperature (water-water) by default | library default | TEvaHea_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TEvaHea_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TEvaHea_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TEvaHea_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
heat_pump_source_mass_flow |
Mass flow rate of the source side of the heat pump [kg/s], the one of the performance data scaled to the nominal heating power by default | library default | mSou_flow_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
mSou_flow_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
mSou_flow_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
mSou_flow_nominal (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
heat_pump_source_outdoor_air |
Whether the evaporator of the air-water heat pump takes the outdoor air of the weather data (true by default) or the constant temperature_heatpump_source (a sweep of the source temperature); Buildings and IDEAS only | library default | useOutdoorAirSource (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
useOutdoorAirSource (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
useOutdoorAirSource (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
useOutdoorAirSource (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
design_outdoor_temperature |
Design outdoor temperature of the heating curve of the air-water heat pump [K], 265.15 (-8 degC, Uccle, NBN EN 12831) by default | library default | TOutDes (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TOutDes (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TOutDes (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TOutDes (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
heating_limit_temperature |
Outdoor temperature above which the air-water heat pump does not heat [K], 289.15 by default | library default | TOutHeaLim (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TOutHeaLim (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TOutHeaLim (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TOutHeaLim (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
minimum_supply_temperature |
Supply temperature of the heating curve of the air-water heat pump at the heating limit [K], 303.15 by default | library default | TSupMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TSupMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TSupMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TSupMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
buffer_temperature_band |
Width of the buffer temperature band switching the air-water heat pump on and off around the supply set point [K], 5 by default | library default | dTHys (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
dTHys (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
dTHys (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
dTHys (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
compressor_minimum_on_time |
Minimum time the compressor of the air-water heat pump runs once started [s], 300 by default | library default | minOnTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
minOnTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
minOnTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
minOnTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
compressor_minimum_off_time |
Minimum time the compressor of the air-water heat pump stays off once stopped [s], 300 by default | library default | minOffTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
minOffTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
minOffTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
minOffTime (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
compressor_minimum_speed |
Lowest speed the compressor of the heat pump runs at, as a fraction of its full speed [1], 0.3 by default. Below the heat this speed delivers the heat pump cannot modulate: it charges its buffer and stops, in cycles (see buffer_temperature_band). At most 0.95, a compressor that hardly modulates: the controller of the speed needs a range between its lowest and its full speed | library default | yComMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
yComMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
yComMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
yComMin (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
compressor_controller_gain |
Gain of the controller holding the supply temperature with the compressor speed [1/K], 0.1 by default: the share of the full speed added per kelvin the condenser outlet is below its set point | library default | kCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
kCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
kCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
kCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
compressor_controller_integral_time |
Integral time of the controller of the compressor speed [s], 300 by default | library default | TiCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TiCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TiCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
TiCom (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump variant) |
heat_pump_data |
Performance data of the heat pump (air_water_heat_pump, ground_source_heat_pump, water_water_heat_pump): an EN 14511 record of Buildings 13 scaled to the nominal heating power (Vitocal251A08, the default of the air-water heat pump, an 8 kW air-water unit; SingleSplitRXM20R, a 2 kW air-air split; WAMAK_WaterToWater_220kW, a 220 kW water-water unit), table for the tables of heat_pump_table_heating_capacity and heat_pump_table_electrical_power, or carnot (the default of the ground-source and water-water heat pumps) for a constant Carnot effectiveness heat_pump_carnot_effectiveness |
library default | - | - | - | - |
heat_pump_carnot_effectiveness |
Carnot effectiveness of the heat pump when heat_pump_data is carnot [1]: the COP is this fraction of the Carnot COP between the condenser outlet plus 5 K and the source minus 5 K (air) or 2 K (water); 0.45 by default, about 3.7 at A7/W35 and 4.4 at B0/W35 | library default | - | - | - | - |
heat_pump_table_source_temperatures |
Source temperatures of the performance tables of the heat pump (heat_pump_data table) [K], the columns of the tables, increasing | library default | - | - | - | - |
heat_pump_table_condenser_temperatures |
Condenser outlet (supply) temperatures of the performance tables of the heat pump (heat_pump_data table) [K], the rows of the tables, increasing | library default | - | - | - | - |
heat_pump_table_heating_capacity |
Heating capacity table of the heat pump (heat_pump_data table) [W]: one row per condenser temperature, the values per source temperature separated by commas, the rows by semicolons, as "4490, 5170, 6470; 4230, 4900, 6260"; a 0 marks a point outside the operating envelope | library default | - | - | - | - |
heat_pump_table_electrical_power |
Electrical power table of the heat pump (heat_pump_data table) [W], laid out as heat_pump_table_heating_capacity | library default | - | - | - | - |
ground_temperature_mean |
Mean temperature of the ground loop of the ground-source heat pump over the year [K], 283.15 by default | library default | TGroMea (ground_source_heat_pump variant) |
TGroMea (ground_source_heat_pump variant) |
TGroMea (ground_source_heat_pump variant) |
TGroMea (ground_source_heat_pump variant) |
ground_temperature_amplitude |
Amplitude of the annual variation of the ground loop temperature of the ground-source heat pump [K], 3 by default (the loop is coldest at the end of the heating season) | library default | TGroAmp (ground_source_heat_pump variant) |
TGroAmp (ground_source_heat_pump variant) |
TGroAmp (ground_source_heat_pump variant) |
TGroAmp (ground_source_heat_pump variant) |
ground_coldest_day |
Day of the year when the ground loop of the ground-source heat pump is coldest [d], 45 (mid-February) by default | library default | groColDay (ground_source_heat_pump variant) |
groColDay (ground_source_heat_pump variant) |
groColDay (ground_source_heat_pump variant) |
groColDay (ground_source_heat_pump variant) |
temperature_initial |
Initial temperature of the boiler and of the tank water [K], 293.15 by default | library default | T_start |
T_start |
T_start |
T_start |
DuctParameters
Elements: duct
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
nominal_mass_flow_rate |
Nominal air mass flow rate through the duct [kg/s] | 100*1.2/3600 |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
dp_nominal |
Pressure drop of the duct at the nominal flow [Pa] | 40.0 |
dp_nominal |
dp_nominal |
dp_nominal |
dp_nominal |
EmissionControlParameters
Elements: emissioncontrol
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
schedule |
Schedule of switching times that toggles the heating set point between the occupied set point and the setback value | 3600*{7, 19} |
schedule |
schedule |
schedule |
schedule |
temperature_heating_setpoint |
Room air temperature heating set point during occupied period [K], 21 degC by default (the design indoor temperature of dwellings) | 294.15 |
THeaSet |
THeaSet |
THeaSet |
THeaSet |
temperature_heating_setback |
Room air temperature heating set point during the setback period (e.g. at night) [K] | 289.0 |
THeaSetBack |
THeaSetBack |
THeaSetBack |
THeaSetBack |
controller_gain |
Gain of controller [1] | 5.0 |
k |
k |
k |
k |
heating_loop_gain |
Gain of the heating loop of the default (PI) control of an emitter [1/K], 0.1 by default: the opening added per kelvin the room is below its set point | library default | kHeaCon (default variant) |
kHeaCon (default variant) |
kHeaCon (default variant) |
kHeaCon (default variant) |
heating_loop_integral_time |
Integral time of the heating loop of the default (PI) control of an emitter [s], 900 by default | library default | TiHeaCon (default variant) |
TiHeaCon (default variant) |
TiHeaCon (default variant) |
TiHeaCon (default variant) |
on_off_band |
Band of the on/off control of an emitter (variant onoff) [K], 0.1 by default: the emitter opens when the room is half the band below its set point and closes when it is half the band above | library default | bandwidth (onoff variant) |
bandwidth (onoff variant) |
bandwidth (onoff variant) |
bandwidth (onoff variant) |
data |
Occupancy data sources | library default | data |
data |
data |
data |
IdealHeatingCoolingParameter
Elements: idealheatingcooling
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
controller_gain |
Gain of the heating and cooling PI controllers, output fraction of the capacity per kelvin of error [1/K] | 0.1 |
k |
k |
k |
k |
controller_integral_time |
Integral time of the heating and cooling PI controllers [s] | 300.0 |
Ti |
Ti |
Ti |
Ti |
cooling_setpoint_schedule |
Day schedule of the cooling set point, rows of time since midnight [s] and set point [K], repeated every day; linear between rows, repeat a time for a step; one row for a constant set point | [0, 300.15] |
TSetCoo |
TSetCoo |
TSetCoo |
TSetCoo |
heating_setpoint_schedule |
Day schedule of the heating set point, rows of time since midnight [s] and set point [K], repeated every day; linear between rows, repeat a time for a step; one row for a constant set point | [0, 293.15] |
TSetHea |
TSetHea |
TSetHea |
TSetHea |
maximum_cooling_power |
Cooling capacity; zero switches cooling off [W] | 1000000.0 |
QCoo_flow_max |
QCoo_flow_max |
QCoo_flow_max |
QCoo_flow_max |
maximum_heating_power |
Heating capacity; zero switches heating off [W] | 1000000.0 |
QHea_flow_max |
QHea_flow_max |
QHea_flow_max |
QHea_flow_max |
radiative_fraction |
Fraction of the heat flow exchanged with the radiative temperature of the zone, the rest with its air [1] | 0.0 |
frad |
frad |
frad |
frad |
OccupancyParameters
Elements: occupancy
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
gain |
Gain to convert from occupancy (per person) to radiant, convective and latent heat in [W/m2] | [35; 70; 30] |
gain |
gain |
gain |
gain |
heat_gain_if_occupied, occupant_density |
Heat gain if occupied | 1/6/4 |
k |
k |
k |
k |
occupancy |
Occupancy table, each entry switching occupancy on or off | 3600*{7, 19} |
occupancy |
occupancy |
occupancy |
occupancy |
ach |
deprecated: the infiltration of a zone is the ach parameter of its space. Infiltration [1/h] |
0.9 |
ACH |
ACH |
ACH |
ACH |
floor_area |
Floor area [m2] | library default | AFlo (co2 variant) |
AFlo (co2 variant) |
- | - |
data |
Occupancy data sources | library default | data |
data |
data |
data |
sensible_heat_per_person |
Sensible heat released per occupant [W]; with the latent heat and the radiant fraction it gives the gain matrix when that one is absent |
library default | taken another way | taken another way | taken another way | taken another way |
latent_heat_per_person |
Latent heat released per occupant [W] | library default | taken another way | taken another way | taken another way | taken another way |
radiant_fraction |
Radiant share of the sensible heat of the occupants [1] | library default | taken another way | taken another way | taken another way | taken another way |
lighting_power_density |
Heat released by the lighting per floor area, all day [W/m2] | library default | lightingPower |
- | taken another way | lightingPower |
lighting_radiant_fraction |
Radiant share of the lighting heat [1], 0.4 by default | library default | lightingRadiantFraction |
- | taken another way | lightingRadiantFraction |
equipment_power_density |
Heat released by the equipment per floor area, all day [W/m2] | library default | equipmentPower |
- | taken another way | equipmentPower |
equipment_radiant_fraction |
Radiant share of the equipment heat [1], 0.4 by default | library default | equipmentRadiantFraction |
- | taken another way | equipmentRadiantFraction |
activity_degree |
Activity level of the occupants of the reduced-order zone [met], 1.2 by default | library default | - | - | taken another way | - |
co2_generation_per_person |
CO2 released per occupant [m3/s], 5.2e-6 by default (CO2 variant) | library default | gCO2 (co2 variant) |
gCO2 (co2 variant) |
- | - |
outdoor_co2_concentration |
CO2 concentration of the outdoor air [ppm], 420 by default (CO2 variant) | library default | ppmOut (co2 variant) |
ppmOut (co2 variant) |
- | - |
PIDParameters
Elements: collectorcontrol
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
controller_type |
Type of controller | Buildings.Controls.OBC.CDL.Types.SimpleController.P |
controllerType |
controllerType |
controllerType |
controllerType |
k |
Gain of controller [1] | 1.0 |
k |
k |
k |
k |
nd |
The higher Nd, the more ideal the derivative block [1] | 10.0 |
Nd |
Nd |
Nd |
Nd |
ni |
Ni*Ti is time constant of anti-windup compensation [1] | 0.9 |
Ni |
Ni |
Ni |
Ni |
r |
Typical range of control error, used for scaling the control error | 1.0 |
r |
r |
r |
r |
td |
Time constant of derivative block [s] | 0.1 |
Td |
Td |
Td |
Td |
ti |
Time constant of integrator block [s] | 0.5 |
Ti |
Ti |
Ti |
Ti |
y_max |
Upper limit of output [1] | 1.0 |
yMax |
yMax |
yMax |
yMax |
y_min |
Lower limit of output [1] | 0.0 |
yMin |
yMin |
yMin |
yMin |
PhotovoltaicParameters
Elements: photovoltaic
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
area |
Module area [m2] | 20.0 |
A |
A |
A |
A |
efficiency |
Module and inverter efficiency [1] | 0.18 |
eta |
eta |
eta |
eta |
azimuth |
Surface azimuth [deg], 0 for south, 90 for west | 0.0 |
- | - | - | - |
tilt |
Surface tilt [deg], 0 for a roof, 90 for a wall | 35.0 |
- | - | - | - |
active_area_fraction |
Share of the module area covered by active cells [1], 0.9 by default | library default | fAct |
fAct |
fAct |
fAct |
inverter_efficiency |
Efficiency of the DC to AC conversion [1], 0.9 by default | library default | eta_DCAC |
eta_DCAC |
eta_DCAC |
eta_DCAC |
power_factor |
Power factor of the inverter [1], 0.9 by default | library default | pf |
pf |
pf |
pf |
tilt_radians |
Surface tilt [rad], from the tilt in degrees | computed | til |
til |
til |
til |
azimuth_radians |
Surface azimuth [rad], from the azimuth in degrees | computed | azi |
azi |
azi |
azi |
PumpParameters
Elements: pump
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
constant_input_set_point |
deprecated: it never reached the pump model and has no effect. Constant input set point | library default | - | - | - | - |
dp_nominal |
Nominal pressure raise [Pa] | 30000.0 |
dp_nominal |
dp_nominal |
dp_nominal |
dp_nominal |
m_flow_nominal |
Nominal mass flow rate [kg/s] | 0.15 |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
RadiatorParameter
Elements: radiator
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
air_temperature_at_nominal_condition, air_temperature |
Air temperature at nominal condition [K] | 293.15 |
TAir_nominal |
TAir_nominal |
TAir_nominal |
TAir_nominal |
dp_nominal |
Pressure drop at nominal mass flow rate [Pa] | 2000.0 |
dp_nominal |
dp_nominal |
dp_nominal |
dp_nominal |
dry_mass_of_radiator_that_will_be_lumped_to_water_heat_capacity, dry_mass |
Dry mass of radiator that will be lumped to water heat capacity [kg] | computed | mDry |
mDry |
mDry |
mDry |
exponent_for_heat_transfer, heat_transfer_exponent |
Exponent for heat transfer | 1.24 |
n |
n |
n |
n |
fraction_of_nominal_mass_flow_rate_where_transition_to_turbulent_occurs, turbulent_transition_fraction |
numerical. Fraction of nominal mass flow rate where transition to turbulent occurs [1] | 0.01 |
deltaM |
deltaM |
deltaM |
deltaM |
fraction_radiant_heat_transfer, radiant_fraction |
Fraction radiant heat transfer [1] | 0.3 |
fraRad |
fraRad |
fraRad |
fraRad |
nominal_heating_power_positive_for_heating, nominal_heating_power |
Nominal heating power (positive for heating) [W] | 5000.0 |
Q_flow_nominal |
Q_flow_nominal |
Q_flow_nominal |
Q_flow_nominal |
number_of_elements_used_in_the_discretization, number_of_elements |
numerical. Number of elements used in the discretization [1] | 1 |
nEle |
nEle |
nEle |
nEle |
radiative_temperature_at_nominal_condition, radiative_temperature |
Radiative temperature at nominal condition [K] | 293.15 |
TRad_nominal |
TRad_nominal |
TRad_nominal |
TRad_nominal |
use_linear_relation_between_m_flow_and_dp_for_any_flow_rate, linearized |
numerical. = true, use linear relation between m_flow and dp for any flow rate | true |
linearized |
linearized |
linearized |
linearized |
use_m_flow_f_dp_else_dp_f_m_flow, from_dp |
numerical. = true, use m_flow = f(dp) else dp = f(m_flow) | false |
from_dp |
from_dp |
from_dp |
from_dp |
water_inlet_temperature_at_nominal_condition, water_inlet_temperature |
Water inlet temperature at nominal condition [K] | 353.15 |
T_a_nominal |
T_a_nominal |
T_a_nominal |
T_a_nominal |
water_outlet_temperature_at_nominal_condition, water_outlet_temperature |
Water outlet temperature at nominal condition [K] | 333.15 |
T_b_nominal |
T_b_nominal |
T_b_nominal |
T_b_nominal |
water_volume_of_radiator, water_volume |
Water volume of radiator [m3] | computed | VWat |
VWat |
VWat |
VWat |
SensorParameters
Elements: temperaturesensor, heatmetersensor
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
nominal_mass_flow_rate |
Nominal mass flow rate through the sensor, used for its dynamics and its small-flow regularization [kg/s] | 0.15 |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
time_constant |
Time constant of the sensor [s], 1 by default; 0 for an ideal sensor | library default | tau |
tau |
tau |
tau |
SpaceParameter
Elements: space
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
average_room_height |
Average room height [m] | 2.0 |
hRoo |
hZone |
- | - |
floor_area |
Floor area [m2] | 20.0 |
AFlo |
taken another way | AZone |
AFlo |
linearize_emissive_power |
numerical. Set to true to linearize emissive power | true |
linearizeRadiation |
- | - | - |
nominal_mass_flow_rate |
Nominal mass flow rate [kg/s] | 0.01 |
m_flow_nominal |
m_flow_nominal (when given) |
- | - |
sensible_thermal_mass_scaling_factor |
Factor for scaling the sensible thermal mass of the zone air volume [1] | 1.0 |
mSenFac |
mSenFac |
mSenFac (when given) |
- |
ach |
Infiltration [1/h] | library default | ACH (infiltration variant) |
taken another way | taken another way | taken another way |
ventilation_schedule |
Day schedule of outdoor air brought into the zone on top of the infiltration, rows of time since midnight [s] and mass flow rate [kg/s], repeated every day (Buildings infiltration variant) | library default | ventilationSchedule (infiltration variant) |
taken another way | - | - |
temperature_initial |
Initial temperature [K] | 294.15 |
T_start |
T_start |
T_start (when given) |
- |
volume |
Air volume of the zone [m3] | computed | - | V |
VAir |
VRoo |
n50 |
Air change rate at a 50 Pa pressure difference, the airtightness of the zone [1/h]; gives the infiltration ach as n50 / n50_to_ach when ach is absent (IDEAS takes it directly) |
library default | taken another way | taken another way | taken another way | taken another way |
n50_to_ach |
Ratio between the air change rate at 50 Pa and the infiltration rate [1] | 20.0 |
taken another way | n50toAch (when given) |
taken another way | taken another way |
interior_convection_coefficient |
Fixed convective heat transfer coefficient of the inside surfaces [W/(m2.K)]; Buildings and the ISO 13790 zone switch to a fixed coefficient (3 and 3.45 by default), the reduced-order zone applies it to its walls, windows, floor and roof (2.7 by default) | library default | hIntFixed |
- | taken another way | hInt |
exterior_convection_coefficient |
Fixed convective heat transfer coefficient of the outside surfaces [W/(m2.K)]; Buildings switches to a fixed coefficient (10 by default), the reduced-order zone applies it to its walls, windows and roof (20 by default) | library default | hExtFixed |
- | taken another way | - |
thermal_mass_class |
Building mass class of the ISO 13790 zone, light, medium or heavy; derived from the heat capacity of the constructions when absent | library default | - | - | - | taken another way |
ground_heat_transfer_factor |
Adjustment factor of the heat transfer through the floor to the ground of the ISO 13790 zone [1], 0.5 by default | library default | - | - | - | b |
shading_reduction_factor |
Factor on the solar gains through the windows for external shading [1]; the ISO 13790 zone applies it always (1 by default), the reduced-order zone when the irradiance exceeds the sunblind threshold (0.7 by default) | library default | - | - | taken another way | shaRedFac |
sunblind_irradiance_threshold |
Irradiance on a window above which the reduced-order zone applies the shading reduction factor [W/m2], 100 by default | library default | - | - | taken another way | - |
SplitValveParameters
Elements: splitvalve
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
dp_nominal |
Pressure drop at nominal mass flow rate, set to zero or negative number at outflowing ports [Pa] | {5000,-1,-1} |
dp_nominal |
dp_nominal |
dp_nominal |
dp_nominal |
fraction_of_nominal_mass_flow_rate_where_transition_to_turbulent_occurs, turbulent_transition_fraction |
numerical. Fraction of nominal mass flow rate where transition to turbulent occurs [1] | 0.3 |
deltaM |
deltaM |
deltaM |
deltaM |
m_flow_nominal |
Mass flow rate; set negative at outflowing ports [kg/s] | 0.15*{1,-1,-1} |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
nominal_mass_flow_rate_for_dynamic_momentum_and_energy_balance, dynamic_nominal_mass_flow_rate |
numerical. Nominal mass flow rate for dynamic momentum and energy balance [kg/s] | library default | mDyn_flow_nominal |
mDyn_flow_nominal |
mDyn_flow_nominal |
mDyn_flow_nominal |
time_constant_at_nominal_flow_for_dynamic_energy_and_momentum_balance, time_constant |
numerical. Time constant at nominal flow for dynamic energy and momentum balance [s] | library default | tau |
tau |
tau |
tau |
use_linear_relation_between_m_flow_and_dp_for_any_flow_rate, linearized |
numerical. = true, use linear relation between m_flow and dp for any flow rate | true |
linearized |
linearized |
linearized |
linearized |
ThreeWayValveControlParameters
Elements: threewayvalvecontrol
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
controller_type |
Type of controller | Buildings.Controls.OBC.CDL.Types.SimpleController.P |
controllerType |
controllerType |
controllerType |
controllerType |
k |
Gain of controller [1] | 1.0 |
k |
k |
k |
k |
nd |
The higher Nd, the more ideal the derivative block [1] | 10.0 |
Nd |
Nd |
Nd |
Nd |
ni |
Ni*Ti is time constant of anti-windup compensation [1] | 0.9 |
Ni |
Ni |
Ni |
Ni |
r |
Typical range of control error, used for scaling the control error | 1.0 |
r |
r |
r |
r |
td |
Time constant of derivative block [s] | 0.1 |
Td |
Td |
Td |
Td |
ti |
Time constant of integrator block [s] | 0.5 |
Ti |
Ti |
Ti |
Ti |
y_max |
Upper limit of output [1] | 1.0 |
yMax |
yMax |
yMax |
yMax |
y_min |
Lower limit of output [1] | 0.0 |
yMin |
yMin |
yMin |
yMin |
supply_temperature_setpoint |
Temperature the valve holds after it, at its temperature sensor [K]. Only a valve with its pump downstream (mixing circuit) can lower the supply temperature; with the pump upstream it can only cut the flow. 363.15 (90 degC) by default, raised 5 K above the highest supply of a storage boiler feeding a valve with its pump upstream (the top of the tank, 15 K above the boiler set point) so that the valve does not close. | library default | - | - | - | - |
ThreeWayValveParameters
Elements: threewayvalve
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
Av |
Av (metric) flow coefficient [m2] | library default | Av |
Av |
Av |
Av |
Cv |
Cv (US) flow coefficient [USG/min/(psi)^(1/2)] | library default | Cv |
Cv |
Cv |
Cv |
Kv |
Kv (metric) flow coefficient [m3/h/(bar)^(1/2)] | library default | Kv |
Kv |
Kv |
Kv |
dp_fixed_nominal |
Nominal pressure drop of pipes and other equipment in flow legs at port_1 and port_3 [Pa] | {2000,0} |
dpFixed_nominal |
dpFixed_nominal |
dpFixed_nominal |
dpFixed_nominal |
dp_valve_nominal |
Nominal pressure drop of fully open valve, used if CvData=Buildings.Fluid.Types.CvTypes.OpPoint [Pa] | 6000.0 |
dpValve_nominal |
dpValve_nominal |
dpValve_nominal |
dpValve_nominal |
fra_k |
Fraction Kv(port_3->port_2)/Kv(port_1->port_2) [1] | 0.7 |
fraK |
fraK |
fraK |
fraK |
fraction_of_nominal_flow_rate_where_linearization_starts_if_y_1, linearization_start_fraction |
numerical. Fraction of nominal flow rate where linearization starts, if y=1 [1] | 0.02 |
deltaM |
deltaM |
deltaM |
deltaM |
m_flow_nominal |
Nominal mass flow rate [kg/s] | 0.15 |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
range_of_significant_deviation_from_equal_percentage_law, equal_percentage_deviation |
Range of significant deviation from equal percentage law [1] | 0.01 |
delta0 |
delta0 |
delta0 |
delta0 |
rangeability |
Rangeability, R=50...100 typically [1] | 50.0 |
R |
R |
R |
R |
rho_std, standard_density |
Inlet density for which valve coefficients are defined [kg/m3] | library default | rhoStd |
rhoStd |
rhoStd |
rhoStd |
use_linear_relation_between_m_flow_and_dp_for_any_flow_rate, linearized |
numerical. = true, use linear relation between m_flow and dp for any flow rate | {true, true} |
linearized |
linearized |
linearized |
linearized |
valve_leakage |
Valve leakage, l=Kv(y=0)/Kv(y=1) [1] | {0.01,0.01} |
l |
l |
l |
l |
flow_coefficient_type |
How the flow coefficients of the valve are given, OpPoint (the nominal pressure drop, the library default), Kv, Cv or Av; without it Kv, Cv and Av are ignored |
library default | taken another way | taken another way | taken another way | taken another way |
actuator_stroke_time |
Time the actuator takes to open or close the valve [s], 120 by default | library default | strokeTime |
riseTime |
strokeTime |
strokeTime |
ValveParameters
Elements: valve
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
av |
Av (metric) flow coefficient [m2] | library default | Av |
Av |
Av |
Av |
cv |
Cv (US) flow coefficient [USG/min/(psi)^(1/2)] | library default | Cv |
Cv |
Cv |
Cv |
dp_fixed_nominal |
Pressure drop of pipe and other resistances that are in series [Pa] | 5000.0 |
dpFixed_nominal |
dpFixed_nominal |
dpFixed_nominal |
dpFixed_nominal |
dp_valve_nominal |
Nominal pressure drop of fully open valve, used if CvData=Buildings.Fluid.Types.CvTypes.OpPoint [Pa] | 10000.0 |
dpValve_nominal |
dpValve_nominal |
dpValve_nominal |
dpValve_nominal |
fraction_of_nominal_flow_rate_where_linearization_starts_if_y_1, linearization_start_fraction |
numerical. Fraction of nominal flow rate where linearization starts, if y=1 [1] | 0.02 |
deltaM |
deltaM |
deltaM |
deltaM |
k_fixed |
Flow coefficient of fixed resistance that may be in series with valve, k=m_flow/sqrt(dp), with unit=(kg.m)^(1/2) | library default | kFixed |
kFixed |
kFixed |
kFixed |
kv |
Kv (metric) flow coefficient [m3/h/(bar)^(1/2)] | library default | Kv |
Kv |
Kv |
Kv |
m_flow_nominal |
Nominal mass flow rate [kg/s] | 0.06 |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
m_flow_nominal |
range_of_significant_deviation_from_equal_percentage_law, equal_percentage_deviation |
Range of significant deviation from equal percentage law [1] | 0.01 |
delta0 |
delta0 |
delta0 |
delta0 |
rangeability |
Rangeability, R=50...100 typically [1] | 50.0 |
R |
R |
R |
R |
use_linear_relation_between_m_flow_and_dp_for_any_flow_rate, linearized |
numerical. = true, use linear relation between m_flow and dp for any flow rate | true |
linearized |
linearized |
linearized |
linearized |
use_m_flow_f_dp_else_dp_f_m_flow, from_dp |
numerical. = true, use m_flow = f(dp) else dp = f(m_flow) | true |
from_dp |
from_dp |
from_dp |
from_dp |
valve_leakage |
Valve leakage, l=Kv(y=0)/Kv(y=1) [1] | 0.0001 |
l |
l |
l |
l |
flow_coefficient_type |
How the flow coefficient of the valve is given, OpPoint (the nominal pressure drop, the library default), Kv, Cv or Av; without it kv, cv and av are ignored |
library default | taken another way | taken another way | taken another way | taken another way |
standard_density |
Inlet density for which the flow coefficients are defined [kg/m3], water at 4 degC by default | library default | rhoStd |
rhoStd |
rhoStd |
rhoStd |
actuator_stroke_time |
Time the actuator takes to open or close the valve [s], 120 by default | library default | strokeTime |
riseTime |
strokeTime |
strokeTime |
VavParameters
Elements: vav
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
nominal_mass_flow_rate |
Nominal air mass flow rate of the damper [kg/s] | 100*1.2/3600 |
m_flow_nominal (default variant) |
m_flow_nominal (default variant) |
m_flow_nominal (default variant) |
m_flow_nominal (default variant) |
damper_dp_nominal |
Pressure drop of the fully open damper at the nominal flow [Pa] | 50.0 |
dpDamper_nominal (default variant) |
dpDamper_nominal (default variant) |
dpDamper_nominal (default variant) |
dpDamper_nominal (default variant) |
fixed_dp_nominal |
Pressure drop of the duct and the other resistances in series with the damper at the nominal flow [Pa] | 50.0 |
dpFixed_nominal (default variant) |
dpFixed_nominal (default variant) |
dpFixed_nominal (default variant) |
dpFixed_nominal (default variant) |
cooling_air_flow_nominal |
Design air mass flow rate for cooling of the VAV box [kg/s] (complex variant) | 100*1.2/3600 |
mCooAir_flow_nominal (complex variant) |
mCooAir_flow_nominal (complex variant) |
mCooAir_flow_nominal (complex variant) |
mCooAir_flow_nominal (complex variant) |
heating_air_flow_nominal |
Design air mass flow rate for heating of the VAV box [kg/s] (complex variant) | 100*1.2/3600 |
mHeaAir_flow_nominal (complex variant) |
mHeaAir_flow_nominal (complex variant) |
mHeaAir_flow_nominal (complex variant) |
mHeaAir_flow_nominal (complex variant) |
room_volume |
Volume of the room the VAV box serves [m3] (complex variant) | 100.0 |
VRoo (complex variant) |
VRoo (complex variant) |
VRoo (complex variant) |
VRoo (complex variant) |
heating_water_inlet_temperature |
Reheat water inlet temperature at the design point [K] (complex variant) | 363.15 |
THeaWatInl_nominal (complex variant) |
THeaWatInl_nominal (complex variant) |
THeaWatInl_nominal (complex variant) |
THeaWatInl_nominal (complex variant) |
heating_water_outlet_temperature |
Reheat water outlet temperature at the design point [K] (complex variant) | 333.15 |
THeaWatOut_nominal (complex variant) |
THeaWatOut_nominal (complex variant) |
THeaWatOut_nominal (complex variant) |
THeaWatOut_nominal (complex variant) |
heating_air_inlet_temperature |
Air inlet temperature of the box at the heating design point [K] (complex variant) | 303.15 |
THeaAirInl_nominal (complex variant) |
THeaAirInl_nominal (complex variant) |
THeaAirInl_nominal (complex variant) |
THeaAirInl_nominal (complex variant) |
heating_air_discharge_temperature |
Discharge air temperature of the box at the heating design point [K] (complex variant) | 298.15 |
THeaAirDis_nominal (complex variant) |
THeaAirDis_nominal (complex variant) |
THeaAirDis_nominal (complex variant) |
THeaAirDis_nominal (complex variant) |
WeatherParameters
Elements: weather
| Parameter | Description | Default | Buildings | IDEAS | AixLib reduced order | ISO 13790 |
|---|---|---|---|---|---|---|
path |
Name of weather data file | library default | filNam |
filNam |
filNam |
filNam |
atmospheric_pressure_source |
Source of the atmospheric pressure, e.g. Buildings.BoundaryConditions.Types.DataSource.File to read it from the weather file; the library default (a constant 101325 Pa) when absent | library default | pAtmSou |
- | pAtmSou |
pAtmSou |
atmospheric_pressure |
Atmospheric pressure [Pa] when it is not read from the weather file, 101325 by default | library default | pAtm |
- | pAtm |
pAtm |
outdoor_co2_concentration |
CO2 concentration of the outdoor air of the IDEAS simulation manager [ppm], 400 by default | library default | - | ppmCO2 |
- | - |
building_height |
Height of the building [m] for the wind speed profile of the IDEAS simulation manager, 10 by default | library default | - | H |
- | - |
default_n50 |
Air change rate at 50 Pa of the IDEAS zones that do not give their own [1/h], 3 by default | library default | - | n50 |
- | - |