Control strategies
trano controls every heated room with a PI loop on the air temperature, whose set point a schedule switches between an occupied value and a setback value (see How ifctrano works). By default the rooms are heated to 21 °C from 7:00 to 19:00 and to 15.85 °C at night. The configuration written by ifctrano can be edited to change this; this example compares the default night setback with a constant set point, on ExampleHOM with its heating model.
Write the configuration:
and set the setback temperature to the set point in the emission control of each space:
spaces:
- id: space_living1_v3g
emissions:
- radiator:
id: radiator_space_living1_v3g
parameters:
nominal_heating_power_positive_for_heating: 3360.0
- valve:
id: valve_space_living1_v3g
control:
emission_control:
id: emission_control_space_living1_v3g
parameters:
temperature_heating_setback: 294.15
then build (and simulate) the model from the edited configuration:
The other parameters of the emission control are temperature_heating_setpoint (294.15 K), schedule
(3600*{7, 19}, the switching times in seconds of the day) and controller_gain (5).
Days 3 to 10 of the year (the first 2 simulated days are a warm-up and are left out).
| Case | Zone | Mean [°C] | Minimum [°C] | Maximum [°C] | Radiator heat [kWh] | Peak radiator heat [kW] | Heat from the generator [kWh] | Gas [kWh] |
|---|---|---|---|---|---|---|---|---|
| Night setback (default) | Living1 | 18.6 | 15.0 | 21.8 | 125 | 4.4 | 148 | 190 |
| Constant set point | Living1 | 20.9 | 19.9 | 22.0 | 162 | 1.6 | 183 | 229 |
What to expect. With the night setback, the rooms cool down at night and are heated up again at 7:00, which takes a power peak; with a constant set point the rooms stay at 21 °C and the radiators deliver a steadier, higher heat.
What the simulation shows. Over days 3 to 10, the living room averages 18.6 °C with the night setback (15.0 °C at night) and 20.9 °C with the constant set point (never below 19.9 °C). Keeping the house at 21 °C needs 162 kWh of radiator heat instead of 125 kWh (30 % more) and 229 kWh of gas instead of 190 kWh (21 % more). The peak heat is lower with the constant set point, 1.6 kW instead of 4.4 kW: the night setback saves energy but asks for a morning reheat.